| Plan Review Notes For Permit 03090897 |
| Permit Number |
03090897 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-10-29 00:00:00 | FAILED | | | ~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | NONE OF THE CORRECTIONS ON THE PROVISO | | | FROM THE PREVIOUS REVIEW WERE CORRECTED | | | ON THE PLAN.PLEASE SEE THE LAST ITEM ON | | | THAT LIST INDICATING THAT ALL PROVISO | | | ITEMS BE CORRECTED ON ANY REVISIONS | | | SUBMITTED FOR REVIEW.PLEASE REVISE THE | | | DRAWING TO CORRECT THESE ITEMS. | | | ALSO NOTE THAT PANEL "C" RATED AND FED | | | @ 60 AMPS NOW HAS A CONNECTED LOAD OF | | | 68.8 AMPS.PLEASE REVISE THE LOAD CALCS | | | AND INCREASE THIS PANEL AND FEEDER SIZE | | | TO HANDLE THE INCREASED LOAD. | | | | | | SUBMIT REVISED DRAWINGS FOR REVIEW.IF | | | THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|