Plan Review Notes
Plan Review Notes For Permit 03090897
Permit Number 03090897
Review Stop B
Sequence Number 2
Notes
Date Text
2003-10-30 00:00:00DENIED
  
 1) SUBMIT A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS OR APPLY
 UNDER A SEPARATE PERMIT. SPECIFY THE
 ANCHORS AND ANCHOR SPACING.
  
 2) SUBMIT DETAILED SHOP DRAWINGS,
 SPECIFICATIONS, CALCULATIONS AND TEST
 DATA FOR THE BUTT GLASS WINDOWS IN HER
 BATH AND THE BREAKFAST ROOM. SEE FBC
 2406.2.
  
 3) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - ARCHED TOP FIXED GLASS WINDOWS
 - RECTANGULAR FIXED GLASS WINDOWS
  
 4) THE PRODUCT APPROVAL FOR THE STORE-
 FRONT WINDOWS IS LIMITED TO A 10FT.
 (120") MULL SPAN AND THE PLANS SPECIFY A
 11FT. 4IN. (136") MULL SPAN. AN ENGINEER
 WILL BE REQUIRED TO CALCULATE THE DESIGN
 PRESSURES FOR A LARGER MULL SPAN BASED
 ON THE TEST DATA AND SUBMIT SIGNED AND
 SEALED CALCULATIONS AND RATIONAL
 ANALYSIS OR THE OPENING SIZE CAN BE
 REDUCED TO 10FT. ON THE PLANS.
  
 5) SUBMIT PRODUCT APPROVALS FOR THE
 MULLION BETWEEN THE SLIDING GLASS DOOR
 AND FIXED GLASS WINDOW AT THE MASTER
 BEDROOM. THE PRODUCT APPROVAL THAT WAS
 SUBMITTED DOES NOT MEET THE REQUIRED
 DESIGN PRESSURES ON THE PLANS. CHECK THE
 TABLES IN THE PRODUCT APPROVAL FOR
 OPENING SIZE, MULL SPAN AND REQUIRED
 PRESSURES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714