| 2003-10-30 00:00:00 | DENIED |
| | |
| | 1) SUBMIT A KEY PLAN AND INSTALLATION |
| | SCHEDULE FOR THE STORM PANELS OR APPLY |
| | UNDER A SEPARATE PERMIT. SPECIFY THE |
| | ANCHORS AND ANCHOR SPACING. |
| | |
| | 2) SUBMIT DETAILED SHOP DRAWINGS, |
| | SPECIFICATIONS, CALCULATIONS AND TEST |
| | DATA FOR THE BUTT GLASS WINDOWS IN HER |
| | BATH AND THE BREAKFAST ROOM. SEE FBC |
| | 2406.2. |
| | |
| | 3) PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - ARCHED TOP FIXED GLASS WINDOWS |
| | - RECTANGULAR FIXED GLASS WINDOWS |
| | |
| | 4) THE PRODUCT APPROVAL FOR THE STORE- |
| | FRONT WINDOWS IS LIMITED TO A 10FT. |
| | (120") MULL SPAN AND THE PLANS SPECIFY A |
| | 11FT. 4IN. (136") MULL SPAN. AN ENGINEER |
| | WILL BE REQUIRED TO CALCULATE THE DESIGN |
| | PRESSURES FOR A LARGER MULL SPAN BASED |
| | ON THE TEST DATA AND SUBMIT SIGNED AND |
| | SEALED CALCULATIONS AND RATIONAL |
| | ANALYSIS OR THE OPENING SIZE CAN BE |
| | REDUCED TO 10FT. ON THE PLANS. |
| | |
| | 5) SUBMIT PRODUCT APPROVALS FOR THE |
| | MULLION BETWEEN THE SLIDING GLASS DOOR |
| | AND FIXED GLASS WINDOW AT THE MASTER |
| | BEDROOM. THE PRODUCT APPROVAL THAT WAS |
| | SUBMITTED DOES NOT MEET THE REQUIRED |
| | DESIGN PRESSURES ON THE PLANS. CHECK THE |
| | TABLES IN THE PRODUCT APPROVAL FOR |
| | OPENING SIZE, MULL SPAN AND REQUIRED |
| | PRESSURES. |
| | |