Plan Review Notes
Plan Review Notes For Permit 03090897
Permit Number 03090897
Review Stop M
Sequence Number 1
Notes
Date Text
2003-09-29 00:00:00DENIED:
 ENERGY CALCULATIONS TO THE MAIN HOUSE
 INDICATE ONE 13 SEER AND ONE 12.6 SEER
 UNIT.PLAN INDICATES ALL EQUIPMENT AS
 12 SEER.PLEASE CORRECT.
  
 PLEASE NOTE, REVISION TO THE 2001
 FBC(M) 601.4, EFFECTIVE JUNE 30,2003:
  
 BALANCED AIR RETURN - RETURN/TRANSFER
 SHALL BE 1 1/2 TIMES THE CROSS SECTIONAL
 AREA (SQ INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM ITS SERVING & THE
 DOOR HAVING AN UNRESTRICTED 1" UNDERCUT.
  
 ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.