| Plan Review Notes For Permit 03090897 |
| Permit Number |
03090897 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-09-25 00:00:00 | PROVISO | | | ~~~~~~~ | | | PLEASE NOTE THAT THE FOLLOWING | | | CORRECTIONS MUST BE DONE TO COMPLY WITH | | | THE 2002 ELECTRICAL CODE. | | | | | | 1} THE EQUIPMENT GROUNDS BEING RAN WITH | | | THE FEEDERS FROM THE METER TO THE FIRST | | | MEANS OF DISCONNECT CREATE A PARALLEL | | | RETURN PATH WITH THE NEUTRAL AND MUST | | | NOT BE INSTALLED PER 250.6(B). | | | | | | 2} THE FEEDER TO PANEL"C" IS MISMARKED | | | ON THE RISER. IT MUST BE SIZED AS PER | | | THE PANEL SCHEDULE WITH A MINIMUM OF | | | #10EQ.GND . | | | | | | 3} THE MASTER BATH RECEPTACLES ARE | | | SHOWNLOCATED MORE THAN 3' FROM THE | | | BASINS & | | | ARE NOT IN COMPLIANCE WITH 210.52(D). | | | | | | 4} THE REFERENCE TO SMOKE DETECTORS | | | BEING FED FROM KITCHEN CIRCUITS MUST BE | | | DISREGARDED OR THAT CIRCUIT MUST BE FED | | | FROM AN AFCI PER 210.12. | | | | | | IF THERE ARE REVISIONS TO THIS SHEET AT | | | ANY TIME,PLEASE INCORPORATE THESE | | | CORRECTIONS WHEN BEING SUBMITTED FOR | | | REVIEW. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|