Plan Review Notes
Plan Review Notes For Permit 03090897
Permit Number 03090897
Review Stop E
Sequence Number 1
Notes
Date Text
2003-09-25 00:00:00PROVISO
 ~~~~~~~
 PLEASE NOTE THAT THE FOLLOWING
 CORRECTIONS MUST BE DONE TO COMPLY WITH
 THE 2002 ELECTRICAL CODE.
  
 1} THE EQUIPMENT GROUNDS BEING RAN WITH
 THE FEEDERS FROM THE METER TO THE FIRST
 MEANS OF DISCONNECT CREATE A PARALLEL
 RETURN PATH WITH THE NEUTRAL AND MUST
 NOT BE INSTALLED PER 250.6(B).
  
 2} THE FEEDER TO PANEL"C" IS MISMARKED
 ON THE RISER. IT MUST BE SIZED AS PER
 THE PANEL SCHEDULE WITH A MINIMUM OF
 #10EQ.GND .
  
 3} THE MASTER BATH RECEPTACLES ARE
 SHOWNLOCATED MORE THAN 3' FROM THE
 BASINS &
 ARE NOT IN COMPLIANCE WITH 210.52(D).
  
 4} THE REFERENCE TO SMOKE DETECTORS
 BEING FED FROM KITCHEN CIRCUITS MUST BE
 DISREGARDED OR THAT CIRCUIT MUST BE FED
 FROM AN AFCI PER 210.12.
  
 IF THERE ARE REVISIONS TO THIS SHEET AT
 ANY TIME,PLEASE INCORPORATE THESE
 CORRECTIONS WHEN BEING SUBMITTED FOR
 REVIEW.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718