Notes
Date Text
2003-10-15 00:00:00DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) FBC* 1804.2.2AREA OF QUESTIONABLE
 SOIL.SUBMIT A GEOTECHNICAL REPORT
 TO VERIFY THE SAFE BEARING CAPACITY OF
 THE SOIL.
  
 3)FBC 1005.4.5 (GLITCH AMENDMENTS
 JULY 1, 2003) REQUIRES AT LEAST ONE
 MEANS OF ESCAPE FROM A DWELLING WHEN
 SHUTTERED FOR IMPACT PROTECTION. THE
 MEANS OF ESCAPE SHALL BE WITHIN THE
 FIRST FLOOR OF THE DWELLING AND CAN NOT
 BE LOCATED IN A GARAGE. OCCUPANTS IN ANY
 PART OF THE DWELLING SHALL HAVE ACCESS
 TO IT WITHOUT HAVING TO PASS THROUGH A
 LOCKABLE DOOR NOT UNDER THEIR CONTROL.
 INDICATE HOW COMPLIANCE WILL BE
 ACHIEVED AT THE MAIN HOUSE AND THE GUEST
 HOUSE.
  
 4) PROVIDE ADDITIONAL DETAILS FOR THE
 MASONRY CHIMNEY. SPECIFY THE REINFORCING
 FOR BEAMS (THERE IS NOTHING TYING IT TO
 THE BEAM SCHEDULE ON A7). SPECIFY THE
 REINFORCING FOR THE PRECAST CHIMNEY CAP
 AND HOW IT WILL BE ANCHORED TO THE
 CHIMNEY.
  
 5) SUBMIT FRAMING DETAILS FOR THE
 CUPOLA. INDICATE THE SIZE AND SPACING OF
 THE STUDS, HEADER SIZE, STRAPPING TO
 PROVIDE LOAD PATH, AND INDICATE THAT
 ADEQUATE BACKING WILL BE PROVIDED FOR
 THE STORM PANELS. (RECOMMEND IMPACT
 GLAZING AT THIS LOCATION)
  
 6)1609.4.3 LOAD REDUCTION.
 WHEN STRUCTURAL EFFECTS DUE TO TWO OR
 MORE LOADS IN COMBINATION WITH DEAD LOAD
 ARE INVESTIGATED IN LOAD COMBINATIONS OF
 1609.4.1 OR 1609.4.2, THE COMBINED
 EFFECTS DUE TO THE TWO OR LOADS MULTI-
 PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD
 LOADS SHALL NOT BE LESS THAN THE EFFECTS
 FROM THE LOAD COMBINATION OF THE DEAD
 LOAD PLUS THE LOAD PRODUCING THE LARGEST
 EFFECTS. INCREAS IN ALLOWABLE STRESS SPE
 CIFIED IN THE MATERIALS SECTIONS OF THIS
 CODE OR A REFRENCED STANDARD SHALL NOT
 BE USED WITH THESE LOAD COMBINATIONS
 EXCEPT THAT A DURATION OF LOAD INCREASE
 SHALL BE PERMITTED IN ACCORDANCE WITH
 CHAPTER 23. UPDATE THE TRUSS ANCHOR
 SCHEDULE. THE 2003 USP CATALOG NO LONGER
 LISTS TAPR 224 CONNECTORS. SPECIFY
 UPLIFT VALUES THAT DO NOT INCLUDE THE
 ONE-THIRD STRESS INCREASE.
  
 7) THE CUPOLA ROOF FRAMING PLAN ON A7
 SPECIFIES CONNECTOR (A) WHICH IS FOR
 TRUSS TO CONCRETE BEAM CONNECTION.
 PLEASE REVISE TO AN APPROPRIATE TRUSS TO
 WOOD CONNECTOR.
  
 8) TRUSS ANCHOR (E) IS SPECIFIED AT THE
 COVERED PATIO WHERE THE UPLIFT EXCEEDS
 THE CAPACITY LISTED IN THE SCHEDULE.
 ANCHOR (A) IS SPECIFIED AT GIRDERS WHICH
 EXCEED ITS CAPACITY. ANCHOR (M) IS
 SPECIFIED FOR A GIRDER WITH 9800# UPLIFT
 SOME BEARING POINTS HAVE NO CONNECTOR
 SPECIFIED. SOME CONNECTOR LOCATIONS ARE
 NOT CLEARLY IDENTIFIED. SEE MARKS ON
 SHEET A7 OF THE PLANS.
  
 9) PROVIDE DETAILS OF ANY SPECIAL
 BRACING REQUIREMENTS FOR CANTILEVERED
 TRUSSES OVER STOREFRONT WINDOW.
  
 10) UPDATE THE CONNECTORS SPECIFIED IN
 THE DETAILS ON SHEET A8. SEMCO IS NO
 LONGER IN BUSINESS.
  
 11) THE GLASS IN THE STOREFRONT WINDOW
 AT THE LIVING ROOM IS REQUIRED TO BE
 SAFETY GLAZING. SEE FBC 2405.2.1(4).
  
 12) SUBMIT MANUFACTURER'S SPECS. AND UL
 LISTING INFORMATION FOR THE BBQ ON THE
 COVERED PATIO.
  
 13) SUBMIT KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS. SPECIFY
 THE ANCHORS AND ANCHOR SPACING. THE
 STORM PANEL DRAWINGS ARE STAMPED FOR ONE
 PERMIT ONLY AND ARE REQUIRED TO BE
 SIGNED AND SEALED BY THE ENGINEER.
  
 14) THE ENERGY CALCULATIONS ARE REQUIRED
 TO BE SIGNED BY THE OWNER/AGENT.
  
 15) THE ENERGY CALCS. ARE CLAIMING THE
 CEILING FAN CREDIT, WHICH REQUIRES A
 MINIMUM OF CEILING FAN IN ALL PRIMARY
 LIVING AREAS. THE PLANS DO NOT INDICATE
 A FAN IN THE LIVING ROOM AS REQUIRED BY
 FBC 13-607.1.A.1. PLEASE REVISE. ALSO
 INDICATE THE SIZE OF THE FANS ON THE
 PLANS. SEE FBC 13-607.A.1 TABLE 6-6.
  
 16) SUBMIT DETAILED SHOP DRAWINGS,
 SPECIFICATIONS, CALCULATIONS AND TEST
 DATA FOR THE BUTT GLASS WINDOWS IN HER
 BATH AND THE BREAKFAST ROOM. SEE FBC
 2406.2.
  
 17) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - RADIUS STORE FRONT WINDOW AT LIVING RM
 - ARCHED TOP FIXED GLASS WINDOWS
 - RECTANGULAR FIXED GLASS WINDOWS
 - METAL DOOR TO MECHANICAL (AHU) ROOM
  
 18) THE PRODUCT APPROVAL SUBMITTED FOR
 THE MULLIONS WILL NOT WORK BETWEEN THE
 SLIDING GLASS DOOR AND FIXED GLASS ABOVE
 AT THE MASTER BEDROOM, BASED ON THE
 TABLES IN THE PRODUCT APPROVAL, THE
 OPENING SIZE, MULLION SPAN AND REQUIRED
 PRESSURES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714