| Date |
Text |
| 2003-10-20 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | |
| | 1) 61G15-23.002(1) 2 SETS OF PLANS HAVE |
| | NO SEAL, SIGNATURE, OR DATE ON THEM. |
| | 61G15-23.002(2) LICENSE NOT SHOWN ON THE |
| | TITLE BLOCK AS REQUIRED. |
| | 2) 11-4.1.6(1)(B) IF EXISTING ELEMENTS, |
| | SPACES, OR COMMON AREAS ARE ALTERED, |
| | THEN EACH SUCH ALTERED ELEMENT, SPACE, |
| | FEATURE, OR AREA SHALL COMPLY WITH THE |
| | APPLICABLE PROVISIONS OF 11-4.1.1 TO |
| | 11-4.1.3. SO PER 11-4.1.3, IF TOILET |
| | ROOMS ARE PROVIDED, THEN EACH PUBLIC AND |
| | COMMON USE TOILET ROOM SHALL COMPLY WITH |
| | 11-4.22. SUBMIT A DETAIL SHOWING COMPLI- |
| | ANCE WILL 11-4.22, 11-4.16, & 11-4.19 |
| | AND ALL SUBSECTIONS OF EACH. - ALSO SEE |
| | SECTION 3401.8.1.1 (BLDG) |
| | 3) THE SANITARY RISER DIAGRAM DOES NOT |
| | REFLECT THE FLOOR PLAN, NOR DOES IS MEET |
| | CODE REQUIREMENTS. 909.1 W/M SHALL NOT |
| | DRAIN INTO THE HORIZONTAL WET VENT OF |
| | THE BATHROOM GROUP OF FIXTURES. 708.10 |
| | WASH MACHINE STACK SHALL HAVE A CLEANOUT |
| | 4' ABOVE THE FLOOR.SEE ATTACHED RISER |
| | FOR AN EXAMPLE OF A RISER THAT MEETS |
| | CODE REQUIREMENTS AND REFLECTS THE FLOOR |
| | PLAN. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |