| Date |
Text |
| 2003-09-24 00:00:00 | UNSAT |
| | ~~~~~ |
| | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | TO THE PLANS AND RESUBMIT FOR REVIEW. |
| | |
| | 1} THE LOAD CALCULATIONS SUBMITTED ARE |
| | FOR DWELLING UNITS. PLEASE SUBMIT |
| | CALCULATIONS AND PANEL SCHEDULES FOR |
| | THE COMMERCIAL APPLICATION BEING |
| | APPLIED PER 220.3. |
| | |
| | 2} PLEASE LABEL CIRCUITS ON THE FLOOR |
| | PLAN AND CORRELATE WITH THE PANEL |
| | SCHEDULE. |
| | |
| | 3} PLEASE NOTE THAT THE RECEPTACLES IN |
| | CLIENT AREAS MUST COMPLY WITH 16.5.1.2 |
| | NFPA-72. |
| | |
| | 4} PLEASE NOTE THAT ALL PLANS |
| | DRAWN BY AN ARCHITECT/ENGINEER CONTAIN- |
| | ING A TITLE BLOCK, MUST BE SIGNED, |
| | DATED AND SEALED BY THE ARCH/ENGINEER OF |
| | RECORD. PER FS/FAC 481.221 & 471.025 |
| | |
| | 5} THE SMOKE DETECTOR IN THE KITCHEN IS |
| | IN VIOLATION OF 8-1.4.2 NFPA-72.MUST BE |
| | A LISTED HEAT DETECTOR OR REMOVED. |
| | |
| | NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110.9, |
| | IF ANY SERVICE EQUIPMENT IS BEING |
| | ADDED OR REPLACED. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |