| 2003-09-23 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION AND RESUBMIT FOR REVIEW. | | | | | | 1} PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110.9. | | | | | | 2} PLEASE PROVIDE LOAD CALCULATIONS AND | | | PANEL SCHEDULES FOR NEW SERVICE. | | | | | | 3} LINE AND LOAD CONDUCTORS ARE IN THE | | | THE SAME ENCLOSURE,MUST BE SEPARATED | | | PE 230.7. | | | | | | 4} THE #6 GEC AT THE REAR HOUSE FOR THE | | | 200 AMP DISCONNECT SHOULD BE A #4 PER | | | 250.66. | | | | | | 5} INDICATE THE SIZE OF THE GUTTERS USED | | | IN FEET AND INCHES, IS THE ONE SHOWN | | | 18" OR 18'?. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|