2003-09-23 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110.9.
  
 2} PLEASE PROVIDE LOAD CALCULATIONS AND
 PANEL SCHEDULES FOR NEW SERVICE.
  
 3} LINE AND LOAD CONDUCTORS ARE IN THE
 THE SAME ENCLOSURE,MUST BE SEPARATED
 PE 230.7.
  
 4} THE #6 GEC AT THE REAR HOUSE FOR THE
 200 AMP DISCONNECT SHOULD BE A #4 PER
 250.66.
  
 5} INDICATE THE SIZE OF THE GUTTERS USED
 IN FEET AND INCHES, IS THE ONE SHOWN
 18" OR 18'?.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW