| Plan Review Notes For Permit 03090703 |
| Permit Number |
03090703 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2004-05-04 00:00:00 | NO MECHANICAL PLANS SUBMITTED FOR REVIEW | | | ENERGY CALCULATIONS SUBMITTED WITH | | | BUILDING PERMIT.NOTE ON PLAN SHEET | | | M/1 INDICATES A/C CONTRACTOR TO SUBMIT | | | PLAN. | | | | | | MECHANICAL CONTRACTOR TO INCLUDE THE | | | FOLLOWING: | | | 1.SUPPLY & RETURN DUCT/GRILLE SIZE, | | | MATERIAL AND LAYOUT. | | | | | | 2.RETURN AIR TO COMPLY WITH THE | | | ATTACHED SCHEDULE. | | | | | | 3.AUXILIARY DRAIN PAN WITH OVERFLOW | | | PROTECTION REQUIRED PER 2001 FBC(M) | | | 307.2.3. |
|