| 2003-10-15 00:00:00 | DENIED:PLANS ARE INCOMPLETE | | | 1.PLEASE PROVIDE DUCT LAYOUT INCLUDING | | | SIZE OF DUCT AND GRILLES. | | | | | | 2.PLEASE NOTE, REVISION TO THE 2001 | | | FBC(M) 601.4, EFFECTIVE JUNE 30,2003: | | | | | | BALANCED AIR RETURN - RETURN/TRANSFER | | | SHALL BE 1 1/2 TIMES THE CROSS SECTIONAL | | | AREA (SQ INCHES) OF THE SUPPLY DUCT | | | ENTERING THE ROOM ITS SERVING & THE | | | DOOR HAVING AN UNRESTRICTED 1" UNDERCUT. | | | | | | ALL SUPPLY AIR INTO THE MASTER SUITE | | | SHALL BE INCLUDED. | | | | | | 3.PLEASE NOTE CODE REFERENCE IS | | | INCORRECT.SHOULD READ 2001 FBC, MECH. | | | | | | 4.NOTE ON PLAN SHEET REFERENCES PLAN | | | SHEET 7/7, NO SUCH DRAWING SUBMITTED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|