| 2003-10-28 00:00:00 | PROVISO | | | ~~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE NOTE THE FOLLOWING IS NOT CODE | | | COMPLIANT. | | | | | | 1} THE NOTE ON SHEET A-4 REGARDING THE | | | SPARE APPLIANCE CIRCUIT BEING "TAPPED" | | | TO BE USED IN THE CLOSET OR BATH DOES | | | NOT CCOMPLY WITH THE INTENT OF | | | 210.52(B)(1) AND CANNOT BE USED IN | | | THESE ROOMS. | | | | | | 2} PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S). PER 210-11-C-3 | | | MUST BE 20A AND #12AWG. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|