Plan Review Notes
Plan Review Notes For Permit 03090673
Permit Number 03090673
Review Stop B
Sequence Number 1
Notes
Date Text
2003-10-15 00:00:00******CORRECTIONS*******
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEPARATE PERMITS REQUIRED.
  
 2.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS.
  
 3.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE
 STAMPED AND RECEIPT ATTACHED TO THE
 APPLICATION.233-5025
  
 4.)SUBMIT TWO COPIES OF ALL
 DOCUMENTATION (PRODUCT APPROVALS,
 PLANS, ENERGY CALCS, SURVEY).
  
 5.)THE TITLE BLOCK REQUIRES THE
 ENGINEER'S LICENSE NUMBER, FAC61G15-23.0
 02.EACH SHEET REQUIRES A SEAL,
 SIGNATURE AND DATE FS471.025.
  
 6.)GENERAL NOTES A1 REFERS TO THE
 WRONG BUILDING CODE.
  
 7.)FEES DUE (VALUE ADJUSTMENT,
 RADON) $28.98.SEE ATTACHED BZ231380.
  
 8.)ENERGY CALCS REQUIRED, FBC13-103.1.
 2.SIGN OWNER/AGENT LINE OF ENERGY
 CALC.
  
 9.)SPECIFY UNDER ATTIC INSULATION
 ON THE WALL SECTION.PLEASE NOTE THAT
 IF A 600C SHORT FORM IS USED FOR THE
 ENERGY CALC, MINIMUM WALL INSULATION
 IS R19 FOR A 2X6 WALL, R30 UNDER ATTIC.
 REVISE WALL SECTION IF NECESSARY.
  
 10.) SPECIFY STRAPS AND CLIPS, WALL
 SECTION (A2).
  
 11.)MTS14 IS NOT IN THE SIMPSON 2003
 CATALOG; CLARIFY.
  
 12.)BOTTOM OF THE FOOTER IS REQUIRED
 TO BE A MINIMUM OF 12" BELOW GRADE
 FBC1804.1.3.
  
 13.)IMPACT PROTECTION REQUIRED
 FBC1606.1.4.PROVIDE TWO COPIES OF
 PRODUCT APPROVALS.