2003-09-26 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 1) MANUF INFORMATION INDICATES 246,000
 BTU'S FOR 6 BURNER GRILL W/OVEN, BUT
 GAS RISER DIAGRAM SHOWS 180,000 BTU'S.
 PLEASE CLAIRFY.
 2) MANUF. INFORMATION FOR 3 POT WOK DOES
 NOT SHOW A LISTING FOR FIXTURE AND DOES
 NOT INDICATE BTU'S. PLEAS SUBMIT MANUF.
 INFORMATION.
 3) UNION REQUIRED AFTER MANUAL SHUT OFF
 VALVE AND UPSTREAM OF FIRE VALVE. REGUL-
 ATOR SHALL BE DOWNSTREAM OF FIRE VALVE.
 4) SUBMIT A CUT SHEET FOR REGULATOR.