| Plan Review Notes For Permit 03090521 |
| Permit Number |
03090521 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-12-04 00:00:00 | ************** UNSAT ************** | | | | | | 1)NOTE: PLEASE SEE NOTES FROM FIRST | | | REVIEW. PLEASE SEE 801, THIS SHEET WAS | | | NOT CORRECTED FOR TITLE BLOCK INFORMAT- | | | -ION. | | | PLEASE SIGN PLANS WITH A SIGNATURE AS | | | REQ'D UNDER FS 471.025 AND FAC 61G15-23. | | | 002. | | | PLEASE BE ADVISED, THE FBPE`S HAS | | | NOTIFIED THIS OFFICE INITIALS ARE NOT | | | ACCEPTABLE AND A MIN OF A VISABLE FIRST | | | AND LAST NAME IS REQ'D. /AND OR HOW | | | SIGNATURE IS ON RECORD WITH THE STATE | | | ENG BOARD. | | | | | | 2)NOTE: PLEASE REMOVE ALL OLD/VOIDED | | | SHEETS AND INSERT NEW SHEETS ONLY INTO | | | TWO COMPLETE SETS FOR REVIEW AND STAMP- | | | -ING. ONE STE OF OLD/VOIDED SHEETS MAY | | | BE SUBMITTED FOR COMPARISON. | | | | | | 3)NOTE: PLEASE SEE TWO CLOUDED REV'S | | | SHOWN ON RISER DIAGRAM AROUND MDP/METER | | | LABELED AS #6. ? PLEASE CLARIFY REV? | | | PLANS APPEARS TO BE SAME AS PREVIOUS. | | | | | | 4)NOTE: PLEASE SEE THAT CODES STILL | | | REF 99 NEC. (801) | | | | | | PLEASE SUBMIT THE ABOVE FOR REVIEW. | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|