Plan Review Notes For Permit 03090521
Permit Number 03090521
Review Stop E
Sequence Number 2
Notes
Date Text
2003-12-04 00:00:00************** UNSAT **************
  
 1)NOTE: PLEASE SEE NOTES FROM FIRST
 REVIEW. PLEASE SEE 801, THIS SHEET WAS
 NOT CORRECTED FOR TITLE BLOCK INFORMAT-
 -ION.
 PLEASE SIGN PLANS WITH A SIGNATURE AS
 REQ'D UNDER FS 471.025 AND FAC 61G15-23.
 002.
 PLEASE BE ADVISED, THE FBPE`S HAS
 NOTIFIED THIS OFFICE INITIALS ARE NOT
 ACCEPTABLE AND A MIN OF A VISABLE FIRST
 AND LAST NAME IS REQ'D. /AND OR HOW
 SIGNATURE IS ON RECORD WITH THE STATE
 ENG BOARD.
  
 2)NOTE: PLEASE REMOVE ALL OLD/VOIDED
 SHEETS AND INSERT NEW SHEETS ONLY INTO
 TWO COMPLETE SETS FOR REVIEW AND STAMP-
 -ING. ONE STE OF OLD/VOIDED SHEETS MAY
 BE SUBMITTED FOR COMPARISON.
  
 3)NOTE: PLEASE SEE TWO CLOUDED REV'S
 SHOWN ON RISER DIAGRAM AROUND MDP/METER
 LABELED AS #6. ? PLEASE CLARIFY REV?
 PLANS APPEARS TO BE SAME AS PREVIOUS.
  
 4)NOTE: PLEASE SEE THAT CODES STILL
 REF 99 NEC. (801)
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]