| Plan Review Notes For Permit 03090521 |
| Permit Number |
03090521 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-10-20 00:00:00 | DENIED: | | | 1.PLEASE NOTE AS PER 2001 FBC(M) | | | 601.4EXCEPTION # 2. TRANSFER GRILLES | | | SHALL USE 50 SQUARE INCHES (OF GRILLE | | | AREA) TO 100 CFM (OF SUPPLY AIR) FOR | | | SIZING THROUGH-THE-WALL TRANSFER | | | GRILLES & USING AN UNRESTRICTED 1 INCH | | | UNDERCUTTING OF DOORS TO ACHIEVE PROPER | | | RETURN AIR BALANCE.PLEASE REVISE | | | TRANSFER GRILLES TO REFLECT PROPER SIZE. | | | | | | 2.PLAN SHEET 603 INDICATES DUCTWORK | | | ABOVE THE RATED CEILING.THIS SHALL NOT | | | COMPROMISE THE HEIGHT REQUIREMENTS FOR | | | THE STAIRWELL OR ACCESS TO THE DUCT | | | SMOKE DETECTOR. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|