| 2003-09-29 00:00:00 | ************** UNSAT ***************** |
| | |
| | 1)NOTE: PLEASE SEE FAC61G15-23.002 FOR |
| | ENGINEERS AND 61G1-16.004 FOR ARCH'S. |
| | PLEASE SEE MISSING INFORMATION REQ'D ON |
| | TITLE BLOCKS FOR BOTH ENGINEERS AND ARCH |
| | 'S. PER FS 471 AND 481 |
| | |
| | 2)NOTE: PLEASE SEE THAT SOME CIRCUITING |
| | FOR EM/EXT LTS ARE NOT PER 700.12E AND |
| | ALSO THERE ARE A FEW MISSING CIRCUIT #`S |
| | |
| | 3)NOTE: PLEASE CLARFIY EM/EXT LTS, THEY |
| | ARE SHOWN AS WHAT APPEARS TO BE COMBO |
| | FIXTURES, HOWEVER FIXTURE SCHEDULE |
| | SHOW THESE AS BEING EXIT ONLY? |
| | PLEASE SEE THAT THERE WOULD BE MANY |
| | LOCATIONS MISSING EM LTS. PLEASE SEE |
| | THAT THERE SOME LOCATION WHERE EM LTS |
| | ARE SHOWN. |
| | PLEASE ALSO SEE SECOND FLR ON 804, WEST |
| | END OF CORRIDOR THAT SEEMS TO NEED AN |
| | ADDITIONAL EM LT. |
| | THERE ARE ALSO FIXTURES THAT ARE SHOWN |
| | JUST AS EXT LTS? |
| | PLEASE SEE 700.12E. |
| | |
| | 4)NOTE: PLEASE SEE CODE ARTS REFERENCED |
| | ON PLANS ARE FROM THE 99 NEC. PLEASE SEE |
| | THAT AS OF JULY 1ST, 2003 THE STATE |
| | ADOPTED THE 2002 NEC. PLEASE ADJUST PLAN |
| | -S AND ARTS FOR 2002. |
| | |
| | 5)NOTE: PLEASE SEE 700.16 FOR LOCATIONS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |