2003-10-16 00:00:00THE PLANS SPECIFY A FIRE DESIGN OF UL
 905 WHICH IN TURN CITES UL LISTED BLOCK
 MANUFACTURERS THAT MUST BE COMPLIED
 WITH AT TIME OF INSPECTION.
  
 SHEET 308 DECLARES A 3/4 HR RATING FOR
 THE STAIR DOORS.FBC TABLE 705.1.2
 REQUIRES A 1 HOURRATING.SEE ALSO,
 FBC 705.1.3.4.PLEASE REVISE AS
 NECESSARY.
  
 SHEETS 309 AND 402 DO NOT CITE THE
 CORRECT MINIMUM DESIGN LOAD CRITERIA AS
 PROVIDED FOR IN FBC 1608.2.
  
 SINCE THE ARCHITECT HAS ASSUMED THE
 STRUCTURAL RESPONSIBILITIES, SEE RULE
 61G-1530 OF THE FL ADMINISTRATIVE CODE
 FOR THE INFORMATION REQUIRED WHEN
 DELEGATING DESIGN RESPONSIBILITY SUCH
 AS THE BAR JOIST DECK SYSTEM FOR THE
 SECOND FLOOR.
  
 PLEASE PROVIDE COMPLETE STRUCTURAL
 CALCLULATIONS DEMOSTRATING COMPLIANCE
 WITH THE FBC CHAPTER 16.
  
 SECTION 1/403.1 CALLS OUT A "SCREW
 ANCHOR" FOR THE ANGLE.WHAT IS THE
 SIZE, DEPTH OF EMBEDMENT AND SPACING OF
 THE SCREW ANCHORS?
  
 SHEET 402 HAS REFERENCE TO SECTION
 4/403 FOR A BEAM TO COLUMN DETAIL THAT
 IS NOT FOUND IN THAT SECTION.PLEASE
 CLARIFY.
  
 SECTION 2/403 HAS A REFERRAL NOTE TO
 3/313 FOR THE DOWELS IN THE FLOOR AND
 THERE IS NO INFORMATION FOR THE DOWELS
 IN SECTION 3/313.PLEASE CLARIFY.
  
 SHEET 603 SHOWS THE A/C DUCT WORK
 PENETRATING THE STAIR SHAFT.THIS IS
 PROHIBITTED BY FBC 1006.1.3.1.PLEASE
 REVISE AS NECESSARY.
  
 THE PLANS MUST BE REVIEWED BY PALM BEACH
 COUNTY FOR IMPACT FEE COORDINATION WITH
 PHASE I.PLEASE HAVE THE PERMIT PLANS
 STAMPED BY THAT OFFICE.
  
 THE DECLARED PERMIT VALUATION OF
 $604,125.00 IS TOO LOW FOR THIS SCOPE
 OF WORK. THE CITY'S ESTIMATE IS
 $986,141.00.THERE ARE $9447.26 IN
 PERMIT FEES REMAINING DUE TO THE CITY
 AS OF THIS DATE.