Plan Review Notes
Plan Review Notes For Permit 03090393
Permit Number 03090393
Review Stop E
Sequence Number 1
Notes
Date Text
2003-09-12 00:00:00************** UNSAT **************
  
 1)NOTE: PLEASE SEE THAT TOTAL VALUE IS
 INCLUDE LABOR AND MATERIALS.
 PLEASE ADJUST VALUE. FBC 104.6.5
  
 2)NOTE: PLEASE SEE THAT PLANS ARE NOT
 COMPLETE FOR ELECTRICAL REWIRE OF HOUSE.
 PLEASE SEE THE FOLLOWING NOTES.
  
 3)NOTE: PLEASE SEE 210.52 FOR MISSING
 RECEPT SPACING.
  
 4)NOTE: PLEASE CLARIFY BATH UPSTAIRS
 SHOWING A RECEPT ON EACH WALL? PLEASE
 SEE THAT RECEPTS ARE NOT PERMITTED IN
 SHOWERS OR BATH TUB AREAS. NEC 300
  
 5)NOTE: PLEASE SEE NFPA-72 8-1.4.2 FOR
 MISSING SD LOCATIONS REQ'D.
  
 6)NOTE: PLEASE CLARIFY # OF RECEPTS
 INSTALLED IN WALK-IN CLOSET. PLEASE NOTE
 THAT CLOSETS ARE NOT REQ'D TO HAVE
 OUTLETS PER 210.52
  
 7)NOTE: PLEASE SEE THAT 2 SM APPL
 CIRCUITS ARE REQ'D FOR MIN. 210.11C1
  
 8)NOTE: PLEASE SEE 210.70 FOR MIN EGRESS
 LIGHTING REQ'D.
  
 9)NOTE: PLEASE SEE 210.52C 1,2,3 ETC FOR
 RECEPT SPACING IN KITCHENS.
  
 10)NOTE: PLEASE SHOW KW RATINGS FOR AHU'
 S, SHOWN W/ #6 AND 2P50.? PLEASE SEE
 424.3B
  
 11)NOTE: PLEASE LIST THE REQ'D ARC FAULT
 PROTECTED CIRCUITS PER 210.12 ON PANEL
 SCHEDULE.
  
 12)NOTE: DISC'S FOR A/C UNITS AND
 LOCATIONS PER 440.11
 RECEPTS PER 210.63
  
 13)NOTE: PLEASE SUBMIT AIC RATING FOR
 NEW MAIN.
  
 PLEASE COMPLETE PLANS TO CONFORM TO NEC
 AND SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  