2003-09-13 00:00:00DENIED
 REFERENCE: FBC-2001 242.2 SWIMMING POOLS
 FLORIDA ADMINISTRATIVE CODE
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW.
 1) FBC-2001424.2.6.6.2 SHOW COMPLIANCE
 WITH ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUF INFO FOR VAC LOCK.
 (GIVE DETAIL OR ADD NOTE)(SUBMITTAL)
 2) FBC-2001 424.2.7.2 PUMPS AND EQUIP-
 MENT SHALL BE MOUNTED ON A SUBSTANTIAL
 BASE IN A MANNER THAT WILL ELIMINATE
 STRAIN ON PIPING. SLAB SHALL BE A NOMIN-
 AL 4" THICK. (DETAIL)
 3) FBC-2001 424.2.9 WATER SUPPLY, LOCAL
 ORD. #2853-95, BACKFLOW REQUIRED ON
 WATER SERVICE. (ADD TO NOTES)
 4) FBC-2001 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 5) FBC-2001 424.2.13.2JOINTS AND CON-
 NECTIONS, FBC PLMG SEC 605.21, PURPLE
 PRIMER REQUIRED ON PVC PIPING. (ADD TO
 NOTES)
 6) FBC-2001 424.2.14.4 CONNECTIONS, ALL
 WATER HEATING EQUIPMENT SHALL BE INSTAL-
 LED WITH FLANGES OR UNION CONNECTIONS
 ADJACENT TO THE HEATER. (ADD TO NOTES)
 7) FBC02001 424.2.15 GAS PIPING SHALL
 COMPLY WITH FBC FUEL GAS. SEPARATE PLANS
 AND PERMIT REQUIRED.
 8) 61G15-23.002(2) LICENSE NUMBER SHALL
 BE ON EACH SHEET.
  