| Plan Review Notes For Permit 03090208 |
| Permit Number |
03090208 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-09-30 00:00:00 | DENIED: | | | PLEASE PROVIDE OUTSIDE AIR CALCULATIONS | | | AS PER 2001 FBC(M) TABLE 403.3. | | | | | | PROVIDE INFORMATION ON EXISTING RTU. | | | INDICATE DUCT SMOKE DETECTOR IF UNIT IS | | | GREATER THAN 2,000 CFM. | | | | | | PLANS OTHERWISE ARE CODE COMPLIANT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|