Plan Review Notes
Plan Review Notes For Permit 03090208
Permit Number 03090208
Review Stop M
Sequence Number 1
Notes
Date Text
2003-09-30 00:00:00DENIED:
 PLEASE PROVIDE OUTSIDE AIR CALCULATIONS
 AS PER 2001 FBC(M) TABLE 403.3.
  
 PROVIDE INFORMATION ON EXISTING RTU.
 INDICATE DUCT SMOKE DETECTOR IF UNIT IS
 GREATER THAN 2,000 CFM.
  
 PLANS OTHERWISE ARE CODE COMPLIANT.
  