| Plan Review Notes For Permit 03090181 |
| Permit Number |
03090181 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-10-01 00:00:00 | PROVISO: | | | 1.PLAN SHEET 2 OF 2 (REVISED) : | | | INDICATES 3M FASTWRAP OR SHAFT FOR | | | CLEARANCE REDUCTION METHOD.PLEASE | | | PROVIDE MANUFACTURER INSTALLATION | | | INSTRUCTIONS ON THE JOBSITE AT THE TIME | | | OF INSPECTION.WELDED DUCT TO BE | | | INSPECTED PRIOR TO COVERING. | | | | | | 2.NOTE REFERENCING TERMINATION OF | | | EXHAUST INDICATES NFPA 96 506.2.14.3, | | | THIS IS INCORRECT SHOULD READ NFPA 96 | | | 4-8.2.1 (A) OR 2001 FBC(M) 506.2.14.3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|