| Plan Review Notes For Permit 03090181 |
| Permit Number |
03090181 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-09-16 00:00:00 | DENIED: | | | INSUFFICIENT INFORMATION FOR REVIEW. | | | PLEASE CLARIFY THE FOLLOWING: | | | | | | 1.TERMINATION OF EXHAUST IN RELATION | | | TO PROPERTY LINE, ADJACENT & CONTINGUOUS | | | BUILDINGS, AS WELL AS AIR INTAKES. | | | 2.ELEVATION OF ROOF WHERE EXHAUST AND | | | SUPPLY FANS ARE LOCATED. (GREATER THAN | | | 16 FT REQUIRES A PERMANENT MEANS OF | | | ACCESS) | | | 3.PLAN SHEET 2 OF 2 INDICATES WOOD | | | CEILING AND ROOF JOIST.PROVIDE A | | | MINIMUM OF 18" CLEARANCE OR INDICATE | | | CLEARANCE REDUCTION METHOD. | | | | | | PLEASE NOTE FOR FUTURE HOOD & GREASE | | | DUCT PERMITS THIS INFORMATION WILL BE | | | REQUIRED AS TO ALLEVIATE PROBLEMS DURING | | | CONSTRUCTION AND AT FINAL INSPECTIONS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|