2003-09-16 00:00:00DENIED:
 INSUFFICIENT INFORMATION FOR REVIEW.
 PLEASE CLARIFY THE FOLLOWING:
  
 1.TERMINATION OF EXHAUST IN RELATION
 TO PROPERTY LINE, ADJACENT & CONTINGUOUS
 BUILDINGS, AS WELL AS AIR INTAKES.
 2.ELEVATION OF ROOF WHERE EXHAUST AND
 SUPPLY FANS ARE LOCATED. (GREATER THAN
 16 FT REQUIRES A PERMANENT MEANS OF
 ACCESS)
 3.PLAN SHEET 2 OF 2 INDICATES WOOD
 CEILING AND ROOF JOIST.PROVIDE A
 MINIMUM OF 18" CLEARANCE OR INDICATE
 CLEARANCE REDUCTION METHOD.
  
 PLEASE NOTE FOR FUTURE HOOD & GREASE
 DUCT PERMITS THIS INFORMATION WILL BE
 REQUIRED AS TO ALLEVIATE PROBLEMS DURING
 CONSTRUCTION AND AT FINAL INSPECTIONS.
  