| Plan Review Notes For Permit 03090174 |
| Permit Number |
03090174 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-09-11 00:00:00 | ************* UNSAT ***************** | | | | | | PLEASE SEE THAT MOST NOTES FROM ORIG | | | REVIEW WERE NOT ADDRESSED. | | | | | | 1)NOTE: PLEASE SEE FS'S 481 AND FAC | | | 61G1-16.004. PLEASE SEE ATTACHED COPY | | | OF FAC FOR INFORMATION MISSING ON TITLE | | | BLOCK. | | | | | | 2)NOTE: PLEASE SHOW CIRCUITING ON PLANS | | | AND CORRELATE WITH PANEL SCHEDULE(S) | | | TO BE SUBMITTED. | | | | | | 3)NOTE: PLEASE SUBMIT ALL INFORMATION | | | AS REQUESTED ON NOTES, 2,3,4,5&6 FROM | | | FIRST REVIEW. | | | | | | 4)NOTE; PLEASE SEE 520/540 ETC FOR | | | MOTION PICT STUDIO'S, THEATERS AND | | | PROJECTOR RMS AND THE LIKE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION AND | | | INFORMATION AS REQUESTED UNDER FIRST | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | | | | PLEASE ALSO SEE ATTACHED LETTER WITH | | | RESPECT TO DESIGN PROFESSIONALS. PER | | | FS 553.80(2)(B) | | | LETTER ATTACHED PER PLUMB PLAN REVIEW. |
|