Notes
Date Text
2003-09-04 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
  
 1) 61G1-16.003 THE PERSONAL SEAL, SIGNA-
 TURE, AND DATE OF THE ARCHITECT SHALL
 APPEAR ON ALL ARCHITECTURAL DOCUMENTS TO
 BE FILED FOR PUBLIC RECORD.
 2) 61G1-16.004(2) TITLE BLOCK. FIRM
 LICENSE NUMBER REQUIRED.
 3) SUBMIT CALCULATIONS FOR MINIMUM FIX-
 TURE FACILITIES PER TABLE 1003.1 (BLDG.)
 AND TABLE 403.1 (PLUMB.). INDICATE NUMB-
 ER OF SEATS PER TABLE 1003.1 FOOTNOTE 1.
 SHOW SQUARE FOOTAGE FOR EACH OCCUPANCY.
 LIBRARY, AUDITORIUM, STORAGE, ECT.
 4) PER TABLE 403.1 A DRINKING FOUNTAIN,
 AND A SERVICE SINK ARE REQUIRED.
 5) SHT A1 HDCP RESTROOM 07, PER SECTION
 11-4.22.2 DOORS SHALL NOT SWING INTO THE
 CLEAR FLOOR SPACE REQUIRED FOR ANY FIX-
 TURE.
 6) SUBMIT A SANITARY & A WATER RISER
 ISOMETRIC. SECTION 104.2.1
 7) INDICATE IF THIS IS A CHANGE OF
 OCCUPANCY. WAS THIS AN ASSEMBLY OCCUPAN-
 CY OR BUSINESS OCCUPANCY? IF CHANGING
 OCCUPANCY, PER SECTION 3401.2.2 THE
 BUILDING, ELECTRICAL, GAS, MECHANICAL,
 AND PLUMBING SYSTEMS SHALL BE MADE TO
 CONFORM TO THE INTENT OF THE TECHNICAL
 CODES AS REQUIRED BY THE BUILDING OFFIC-
 IAL.
  