Plan Review Notes
Plan Review Notes For Permit 03090174
Permit Number 03090174
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2003-09-04 00:00:001) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
  
 2) PLEASE INDICATE TOTAL OCCUPANT
 LOADS WHEN THE BUILDING IS OCCUPIED.
  
 3) NO MENTION ON THE PLANS WITH
 REGARDS TO THE EXISTING FIRE
 SPRINKLER SYSTEM. PLEASE MAKE
 REFERENCE ON THE PLANS THAT THE
 BUILDING IS FIRE SPRINKLER PROTECTED.
  
 4) ARE THERE ANY PLANNED WAITING SPACES
 FOR THE ESTABLISHMENT.
  
 5) ARE THE SEATS IN THE AUDITORIUM
 FIXED OR NON-FIXED.
  
 6) NO SMOKING SIGNS SHALL BE POSTED
 WHERE SMOKING IS PROHIBITED.
  
 7) NO OPEN FLAME OR PYROTECHNICS
 ALLOWED WITHIN THE BUILDING.
  
 8) THE TECH BOOTH IF FILM OR VIDEO
 PROJECTORS OR SPOTLIGHTS USING LIGHT
 SOURCES ARE PLANNED, IT SHALL COMPLY
 WITH APPLICABLE CODE REQUIREMENTS.
  
 9) THE TREADS NEAR THE TECH BOOTH
 SHALL BE AT LEAST 13" WIDE SINCE THERE
 ARE LESS THAN THREE RISERS WILL
 BE PRESENT.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910