| Plan Review Notes For Permit 03090174 |
| Permit Number |
03090174 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-09-05 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION,MAKE NECESSARY CHANGES IN | | | PLANS FOR CODE COMPLIENCE AND RESUBMIT | | | FOR REVIEW. | | | | | | 1} THE ARCHITECTS SEAL AND TITLE BLOCK | | | MUST CONFORM TO 61G1-16.001 AND | | | 61G1-16.004 RESPECTIVELY. | | | | | | 2} PLEASE PROVIDE LOAD | | | CALCULATIONS,PANEL SCHEDULES AND | | | INDICATE THE SIZE OF THE EXISTING | | | SERVICE INTENDED TO SUPPLY THE POWER | | | FOR THE SCOPE OF WORK SHOWN. | | | | | | 3} PLEASE SHOW ALL CONTINUOUS LOADS @ | | | 125% PER 210.19(A) & 215.2. | | | | | | 4} SHOW ALL TRACK LIGHTING PER 210.12(B) | | | | | | 5} PLEASE SHOW EGRESS LIGHTING PER | | | NFPA-101,7.8. | | | | | | 6} INDICATE BRANCH CIRCUIT NUMBERS ON | | | DRAWINGS PER 210.4(D). | | | | | | NOTE: THE USE OF THIS OCCUPANCY MUST | | | COMPLY WITH 518 & 520,ALSO ARTICLE 540 | | | IF "TECH BOOTH" IS TO CONTAIN A | | | PROJECTOR | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|