| Plan Review Notes For Permit 03090174 |
| Permit Number |
03090174 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-09-08 00:00:00 | | | | BUILDING COMMENTS | | | -------- -------- | | | | | | 1] | | | SUBMIT OCCUPANT LOAD CLARIFICATION, FBC | | | 1003.1 | | | | | | 2] | | | PROVIDE LIFE SAFTY EGRESS PLAN PER FBC | | | 1019.1 | | | | | | 3] | | | USE 'B' TYPE CORRIDOR SEPERATION WALL | | | AT WEST AND SOUTH AUDITORIUM WALLS. FBC | | | 704.2.4 | | | | | | 4] | | | CORRIDOR #1 AT RESTROOM AREA IS A DEAD | | | END, MAXIMUM CORRIDOR LENGTH IS 20'. FBC | | | 1004. | | | | | | 5] | | | STATE OF FLORIDA ACCESSABILITY WAIVER | | | IS REQUIRED FOR THE ELEVATED SEATING | | | AREA. | | | | | | | | | L.MARTINEZ 805-6710 |
|