| 2004-11-19 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 805 6716 |
| | E-MAIL: [email protected] |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | F.S.= FLORIDA (STATE) STATUTE |
| | |
| | REVISION SUBMITTED 10/29/04 FOR SHEETS |
| | A-3, A-4, A-5, A-6 AND E-1 |
| | |
| | ***NOTE*** |
| | FOR THE SECOND TIME, NONE OF THE |
| | REDLINED NOTES HAVE BEEN INCORPORATED, |
| | BY THE ARCHITECT, ON THE REVISED SHEETS. |
| | THESE NOTES HAVE AREADY BEEN REDLINED |
| | TWICE BY THIS OFFICE. THE PROVISO SENT |
| | OUT WITH THE PERMIT APPROVED PLANS |
| | STATED "ANY REVISIONS TO THIS PERMIT, |
| | SUBMITTED WITHOUT INCORPORATING THE |
| | REDLINED NOTES WILL BE DENIED." |
| | |
| | 1) THE REVISION SHALL INCLUDE THE NOTES/ |
| | CHANGES THAT WERE REDLINED ON SHEETS |
| | A-1, A-3 AND THE TITLE SHEET.ALSO THE |
| | REVISED SHEETS STILL DO NOT INCLUDE THE |
| | M. SIMON & ASSOCIATES STREET ADDRESS |
| | (SEE REDLINED PLANS), THE ARCHITECT'S |
| | PRINTED LICENSE NUMBER OR THE |
| | ARCHITECT'S PRINTED NAME (SEE FLORIDA |
| | ADMINISTRATIVE CODE 61G1-16.003 & 004). |
| | SUBMIT REVISED SHEETS. |
| | |
| | 2) FBC 803.3SHEET A-5, WALL SECTIONS |
| | 10 AND 12.REVISION FROM PAINTED |
| | DRYWALL TO MDF PANELS.THE MDF PANELS |
| | SHALL HAVE A FLAMESPREAD RATING OF LESS |
| | THAN 200.ADD A NOTE TO THE PLANS. |
| | |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |