| 2003-12-08 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 805 6716 |
| | E-MAIL: [email protected] |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | |
| | FOR CONSISTENCY, THE FOLLOWING COMMENTS |
| | ARE NUMBERED AS PER THE BUILDING PLAN |
| | REVIEW OF 9/12/03: |
| | |
| | 2) FL. ADMIN CODE 61G1-16.004THIS |
| | COMMENT HAS NOT BEEN PROPERLY ADDRESSED. |
| | THE TITLE BLOCKS ON THE ARCHITECTURAL |
| | PLANS STILL DO NOT INCLUDE THE STREET |
| | ADDRESS OF THE ARCHITECTURAL BUSINESS. |
| | ALSO: THE SIGNATURES ON THE REVISED |
| | SHEETS ARE NOT DATED.THESE ITEMS ARE |
| | REQUIRED ON ALL DOCUMENTS PREPARED BY AN |
| | ARCHITECT AND BEING FILED FOR PUBLIC |
| | RECORD, PER 481.221 FS. |
| | |
| | 7) FBC 704.3.1SHEET A-3.BOTH TENANT |
| | SEPARATION WALLS WERE ORIGINALLY |
| | SPECIFIED AS 1-HOUR FIRE-RATED U.L #465. |
| | THE REVISED PLAN NOW SHOWS ONLY THE |
| | RIGHT SIDE TENANT SEPARATION WALL AS |
| | TYPE 1 (REF. WALL LEGEND), WHICH IS |
| | 1-HOUR RATED.AMEND THE PLAN TO STATE |
| | THE REQUIRED 1-HOUR FIRE-RATING FOR THE |
| | LEFT SIDE TENANT SEPARATION WALL ALSO. |
| | |
| | 8) COVER SHEET, SHEET A-2 AND SHEET A-5. |
| | ITEMS THAT WERE REDLINED AS A RESULT OF |
| | THE PREVIOUS PLAN REVIEW HAVE NOT BEEN |
| | CORRECTED ON THE REVISED SET.THESE |
| | ITEMS HAVE BEEN REDLINED AGAIN ON THE |
| | REVISED PLANS. |
| | |
| | 9) IF NEW PLAN SHEETS ARE REQUIRED, IN |
| | ORDER TO ADDRESS THE ABOVE COMMENTS, THE |
| | OLD SHEETS SHALL BE REMOVED AND THE NEW |
| | SHEETS INSERTED.ONE COPY OF EACH OLD |
| | SHEET SHALL BE INCLUDED WITH THE |
| | RESUBMITTAL FOR COMPARISON OF REVISIONS. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | TELEPHONE: (561) 805 6716ROBERT BROWN |
| | E-MAIL: [email protected] |