Plan Review Notes
Plan Review Notes For Permit 03090080
Permit Number 03090080
Review Stop E
Sequence Number 3
Notes
Date Text
2003-12-16 00:00:00***************** UNSAT ****************
  
 PLEASE SEE THERE ARE A COMPLETELY NEW
 COMMENTS DUE TO THE PLANS/SERVICE/RISER
 BEING CHANGED FROM FIRST REVIEW.
  
 1)NOTE: PLEASE SHOW ALL EQUIPMENT
 GROUNDING CONDUCTORS PER 250.110, 250.24
 AND SIZE PER 250.122.
  
 2)NOTE: PLEASE SEE ORIG PLANS SHOWS
 EXISTING METERSFOR 4209 & 4211, PLANS
 NOW SHOW A NEW 400A METER AND DISC YET,
 TWO EXISTING METERS ARE STILL BEING
 SHOWN AND THESE ARE NOT ON RISER DIAGRAM
 ?? PLEASE ALSO SHOW HOW AND WHERE NEW
 SERVICE IS BEING FED? FROM EXISTING
 OR NEW GUTTER/RISER ETC???215.5
 IF SERVICE IS BEING FROM EXSITNG RISER
 ETC, PLEASE PROVIDE LOAD CALCS AND SIZE
 OF EXISTING SEC'S.
  
 3)NOTE: PLEASE SEE RISER SHOWS NEW
 PANEL(MDP) "G" YET PLANS DO NOT SHOW
 A NEW PANEL SCHEDULE FOR THIS?????
  
 4)NOTE: PLEASE SEE THAT PLANS DO NOT
 SHOW NEW DISC'S THAT ARE NOW SHOWN IN-
 -BETWEEN MDP AND PANELS?
  
 5)NOTE: PLEASE SHOW GROUNDING ELECTRODE
 SYSTEM FOR NEW SERVICE. 250.50
  
 6)NOTE: PLEASE SEE CONDUIT FILL TABLES
 BEING THAT AN EQUIPMENT GRND IS REQ'D
 AND VERIFY SIZE OF CONDUITS.
  
 7)NOTE: PLEASE SEE THAT DUE TO THE
 AMOUNT OF WORK BEING DONE "SHOW WINDOW"
 RECEPTS WILL BE REQ'D IF NOT EXSITING
 PER 210.62.
 FBC CHAPTER 34
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]