| 2003-10-01 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 1 |
| | |
| | A) THE FOLLOWING INFORMATION IS REQUIRED |
| | FOR GAS PERMIT. (SEPARATE PERMIT REQ'D) |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. (SEE RED LINE COMMENTS ON |
| | PLANS) |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | 3. TYPE OF GAS, (LP OR NATURAL) |
| | 4. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2001 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.5.2 AND TABLES 402(1) THRU |
| | 402(34). THERE IS CONFLICTING INFORMAT- |
| | ION ON PLANS. ONE NOTE STATES 40 DRYER |
| | UNITS, BUT THE COUNT INDICATES 36 DRYERS |
| | ALSO TOTAL BTU'S INCORRECT. PLEASE |
| | CLAIRFY. |
| | 5. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES (A)(3). DISTANCE TO |
| | MOST REMOTE ON NOTES SAYS 89 FEET BUT |
| | THE DROP FOR THE DRYERS IN AREA 2 ARE |
| | NOT ADDED. PLEASE RECALCULATE. |
| | 6. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | TABLE 402(2) SHOWS 3,250,000 MAX FOR 3" |
| | PIPE. TOTAL BTU'S SEEM TO BE 3,605,000. |
| | EITHER 4" PIPE WILL HAVE TO BE USED OR |
| | A 2 LB SYSTEM CAN BE USED REDUCING MAXI- |
| | 7. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2 |
| | 8. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | 9. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND |
| | APPURTENANCES PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | 10) SECTION 409.7 EACH GAS APPLIANCE |
| | SHALL BE PROVIDED WITH A GAS SHUTOFF |
| | VALVE INSTALLED UPSTREAM OF THE UNION. |
| | SHOW ON GAS RISER DIAGRAM. |
| | B) SHT 6 OF 7 WATER RISER DIAGRAM. SEC |
| | 604.9 WATER HAMMER ARRESTORS SHALL BE |
| | INSTALLED FOR ALL QUICK CLOSING VALVES. |
| | THEY SHALL BE INSTALLED AT THE WASHMACH- |
| | INES AND SIZED FOR EACH RUN. ALL WATER |
| | HAMMER ARRESTORS SHALL BE LOCATED NEAR |
| | THE FIXTURES IN AN "EFFECTIVE RANGE" |
| | PER PDI-WH 201 AND MANUF. INSTALLATION |
| | INSTRUCTIONS NOT IN THE CEILING AS SH0WN |
| | C) SHT 6 OF 7 WATER HEATER. THERMAL |
| | EXPANSION PROTECTION REQUIRED PER SEC |
| | 607.3.2 |
| | |