| Plan Review Notes For Permit 03090080 |
| Permit Number |
03090080 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-09-10 00:00:00 | ***********UNSAT *************** | | | | | | 1)NOTE: PLEASE SHOW ARE REQ'D FOR EM LTS | | | TO MEET 700.16 | | | | | | 2)NOTE: OK | | | | | | | | | 3)NOTE: PLEASE SHOW LOAD CALCULATIONS | | | PER NEC 220, PLEASE ALSO SHOW ANY | | | CONTINUOUS AT 125%. 215.3/230.42 ETC. | | | | | | 4)NOTE: PLEASE CLARIFY NEW OR EXISTING | | | SIGN CIRCUIT PER 600.5 | | | | | | PLEASE SEE FIRE REVIEW COMMENTS FOR | | | ANY CHANGES THAT MAY BE NEEDED FOR | | | ELECTRICAL PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|