2003-09-10 00:00:00***********UNSAT ***************
  
 1)NOTE: PLEASE SHOW ARE REQ'D FOR EM LTS
 TO MEET 700.16
  
 2)NOTE: OK
  
  
 3)NOTE: PLEASE SHOW LOAD CALCULATIONS
 PER NEC 220, PLEASE ALSO SHOW ANY
 CONTINUOUS AT 125%. 215.3/230.42 ETC.
  
 4)NOTE: PLEASE CLARIFY NEW OR EXISTING
 SIGN CIRCUIT PER 600.5
  
 PLEASE SEE FIRE REVIEW COMMENTS FOR
 ANY CHANGES THAT MAY BE NEEDED FOR
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  