Notes
Date Text
2003-09-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 AMENDMENTS, CHAPTER
 ONE, ADMIN. CODE
 FLORIDA ADMINISTRATIVE CODE
  
 1) SHT P.2 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE REQUIREMENTS, NOR DOES IT
 REFLECT THE FLOOR PLAN.
 A) WATER CLOSETS SHALL NOT BE DOUBLE
 TRAPPED. SECTION 1002.1
 B) 2" MINIMUM TRAP FOR WASH MACHINE.
 TABLE 709.1
 C) LAV NOT VENTED IN SHOWER BATH 2ND
 FLOOR. SECTION 901.2.1
 2) SEE ATTACHED SHEET FOR EXAMPLE OF A
 SANT. RISER DIAGRAM THAT REFLECTS THE
 FLOOR PLAN AND MEETS CODE REQUIREMENTS.
 3) 61G1-16.004 FIRM LICENSE NUMBER REQ-
 UIRED ON EACH SHEET IN TITLE BLOCK.
  
 REVIEW BY KEN STEVENS