| Plan Review Notes For Permit 03090051 |
| Permit Number |
03090051 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-09-15 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 AMENDMENTS, CHAPTER | | | ONE, ADMIN. CODE | | | FLORIDA ADMINISTRATIVE CODE | | | | | | 1) SHT P.2 SANITARY RISER DIAGRAM DOES | | | NOT MEET CODE REQUIREMENTS, NOR DOES IT | | | REFLECT THE FLOOR PLAN. | | | A) WATER CLOSETS SHALL NOT BE DOUBLE | | | TRAPPED. SECTION 1002.1 | | | B) 2" MINIMUM TRAP FOR WASH MACHINE. | | | TABLE 709.1 | | | C) LAV NOT VENTED IN SHOWER BATH 2ND | | | FLOOR. SECTION 901.2.1 | | | 2) SEE ATTACHED SHEET FOR EXAMPLE OF A | | | SANT. RISER DIAGRAM THAT REFLECTS THE | | | FLOOR PLAN AND MEETS CODE REQUIREMENTS. | | | 3) 61G1-16.004 FIRM LICENSE NUMBER REQ- | | | UIRED ON EACH SHEET IN TITLE BLOCK. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|