| 2003-09-12 00:00:00 | ************ USNAT ***************** |
| | |
| | 1)NOTE: PLEASE SEE ATTACHED COPY OF THE |
| | FAC 61G1-16.004 FOR ARCH'S. PLEASE SEE |
| | MISSING LICENSE INFORMATION REQ'D ON |
| | TITLE BLOCK. |
| | |
| | 2)NOTE: PLEASE SEE SEC'S, PLEASE SIZE |
| | PER 310.15/ 310.16 SHOWN AS #1?? |
| | PLEASE ALSO SEE FEEDERS TO PANEL. |
| | |
| | 3)NOTE:PLEASE SEE 250.110/250.122 FOR |
| | MISSING EQUIPMENT GROUNDING CONDUCTOR |
| | FROM MAIN TO PANEL.250.24 |
| | |
| | 4)NOTE: PLEASE SEE 250.50 FOR ALL POINTS |
| | OF ATTACHMENT REQ'D FOR GROUNDING ELEC- |
| | -TRODE CONDUCTOR. ONLY SHOWN TO GRND ROD |
| | |
| | 5)NOTE: PLEASE SEE 225.30 FOR MEANS |
| | OF DISC AT DETACHED STRUCTURES. PLEASE |
| | SEE THAT MLO PANEL AT GARAGE IS NOT |
| | PERMITTED TO FEED MAIN HOUSE W/OUT |
| | MEANS OF DISC. |
| | |
| | 6)NOTE: PLEASE SEE THAT SD IS NOT |
| | PERMITTED IN KITCHEN NFPA-72 8-1.4 |
| | |
| | 7)NOTE: SD'S REQ'D INSIDE AND OUTSIDE |
| | ALL SLEEPING RMS AND ON EACH LEVEL OF |
| | A MULTI-LEVEL RESIDENCE. SD REQ'D TO |
| | BE IN THE IMMEDIATE VICINTY OF STAIRS |
| | LEADING TO FLR ABOVE. NFPA-72 8-1.4.2 |
| | 2-2.1.1.1,2-5.2.1.6 |
| | |
| | 8)NOTE: PLEASE CLARIFY WHAT APPEARS TO |
| | BE AN ISLAND IN KITCHEN? IF SO THEN A |
| | GFI RECEPT WILL BE REQ'D. 210.52C2 |
| | 210.8A6 |
| | |
| | 9)NOTE: PLEASE SEE 210.70 FOR LIGHTING |
| | REQ'D FOR EGRESS AREAS. SHOWN AS J-BOX |
| | LIFE SAFTEY CODE 101 5-8 |
| | |
| | 10)NOTE: PLEASE SEE 210.52 FOR RECEPT |
| | SPACING. ONLY MISSING A COUPLE. |
| | UPSTAIRS. |
| | |
| | 11)NOTE: PLEASE SUBMIT A PANEL SCHEDULE |
| | WITH ALL MIN REQ'D CIRCUITS. PLEASE |
| | CORRELATE WITH PLANS. |
| | 215.5 |
| | PLEASE LIST BATH(S) AS 210.52D/210.11C3 |
| | PLEASE LIST ALL REQ'D ARC FAULT PROTECT- |
| | ED CIRCUITS PER 210.12 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. PLEASE SEE THAT SERVICE WILL |
| | BE REVISED AND W/OTHER INFORMATION |
| | NEEDED PLANS MAY HAVE ADDTIONAL COMMENTS |
| | DUE TO THE FACT OF SOME CHANGES. |
| | IF THERE ARE ANY QUESTIONS, PLEASE CALL. |
| | |