2003-10-08 00:00:00BUIILDING DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR ALL EXTERIOR WINDOWS AND
 DOORS.
  
 4) PROVIDE (2) PRODUCT APPROVALS, KEY
 PLANS AND INSTALLATION SCHEDULES
 INDICATING THE SPECIFIC TYPES OF ANCHORS
 TO BE USED FOR STORM PANELS. INDICATE
 THE MOUNTING TYPES AND ANCHOR SPACING.
  
 5) SUBMIT TWO COPIES OF A SURVEY.
  
 6) FBC* 1804.2.2AREA OF QUESTIONABLE
 SOIL.SUBMIT A GEOTECHNICAL REPORT
 TO VERIFY THE SAFE BEARING CAPACITY OF
 THE SOIL.
  
 7) THE FLOOD ZONE INDICATED ON SHEET A1
 AS 'A5' IS INCORRECT. THE PROPERTY IS IN
 A 'C' ZONE. PLEASE CORRECT.
  
 8) THE AREA OF THE FRONT PORCH IS NOT
 INCLUDED IN THE AREA LISTED FOR THE
 COVERED PORCHES ON A1 AND A2. PLEASE
 CORRECT.
  
 9)SPECIFY SAFETY GLAZING FOR THE WINDOWS
 THAT ARE WITHIN THREE FEET HORIZONTALLY
 OF A TUB OR SHOWER AND ADJACENT TO DOORS
 AS REQUIRED BY FBC 2405.2.
  
 10)THE DIMENSIONS OF THE UPPER AND LOWER
 REAR PORCHES ARE NO INDICATED ON A2 AND
 A3 OF THE PLANS.
  
 11) SUBMIT MANUFACTURER'S SPECIFICATIONS
 AND UL LISTING INFORMATION FOR THE PRE-
 FAB FIREPLACE AND FLUE PIPE.
  
 12) PROVIDE STRAPPING AND CONNECTOR
 DETAILS FOR THE CHIMNEY.
  
 13) INDICATE THE FIREBLOCKING AT THE
 CHIMNEY AT THE FLOOR AND CEILING AS
 REQUIRED BY FBC 2305.
  
 14) 2305.2.2 FLOOR/CEILING ASSEMBLIES
 SINGLE FAMILY DWELLINGS. IN FLOOR/CEIL-
 ING ASSEMBLIES SEPARATING USEABLE SPACE
 INTO 2 OR MORE APPROXIMATE AREAS WITH NO
 AREA GREATER THAN 500 SQ FT. DRAFTSTOP-
 PING SHALL BE PROVIDED PARALLEL TO THE
 MAIN FRAMING MEMBERS. INDICATE THE
 LOCATIONS AND MATERIALS TO BE USED.
  
 15) THE MASTER BATH WINDOW SHOWN ON THE
 ELEVATION ON A5 LARGER THAN INDICATED IN
 THE WINDOW SCHEDULE.
  
 16) DETAIL 4 ON S2 SPECIFIES 5/8" CDX
 WALL SHEATHING AND THE DETAILS ON A4
 SPECIFY 1/2" EXTERIOR "GRAND" PLYWOOD.
 PLEASE CORRECT.
  
 17) REVISE DETAIL 2 ON A7. THE SPACE
 BELOW THE BOTTOM RAIL OF THE GUARDRAIL
 IS REQUIRED TO REJECT A 2" SPHERE PER
 FBC 1015.3.
  
 18) SPECIFY THE CONNECTIONS FOR THE
 NEWEL POSTS AND RAILS AT THE INTERIOR
 STAIRS AND GUARDRAIL.
  
 19) SPECIFY THE FASTENERS AND SPACING
 AT THE PLYWOOD PORCH CEILINGS.
  
 20) PS-1 ON S1 SPECIFIES 3/4" ROOF
 SHEATHING AND 5/8" ROOF SHEATHING IS
 SPECIFIED ON THE OTHER SHEETS. PLEASE
 CLARIFY.
  
 21) UPDATE RC-5 ON S1 TO ACI 318-02,
 WHICH IS THE CURRENT STANDARD REFERENCED
 BY THE 2001 FBC.
  
 22)THE ACCESS OPENINGS TO THE FOUNDATION
 REQUIRED BY FBC 1804.6.3.2, APPEAR TO BE
 BLOCKED BY THE PORCHES AND ARE NOT
 ACCESSIBLE TO THE EXTERIOR.
  
 23)1609.4.3 LOAD REDUCTION.
 WHEN STRUCTURAL EFFECTS DUE TO TWO OR
 MORE LOADS IN COMBINATION WITH DEAD LOAD
 ARE INVESTIGATED IN LOAD COMBINATIONS OF
 1609.4.1 OR 1609.4.2, THE COMBINED
 EFFECTS DUE TO THE TWO OR LOADS MULTI-
 PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD
 LOADS SHALL NOT BE LESS THAN THE EFFECTS
 FROM THE LOAD COMBINATION OF THE DEAD
 LOAD PLUS THE LOAD PRODUCING THE LARGEST
 EFFECTS. INCREAS IN ALLOWABLE STRESS SPE
 CIFIED IN THE MATERIALS SECTIONS OF THIS
 CODE OR A REFRENCED STANDARD SHALL NOT
 BE USED WITH THESE LOAD COMBINATIONS
 EXCEPT THAT A DURATION OF LOAD INCREASE
 SHALL BE PERMITTED IN ACCORDANCE WITH
 CHAPTER 23. PLEASE REVISE THE CONNECTOR
 SCHEDULE ON S4 TO VALUES THAT DO NOT
 INCLUDE THE STRESS INCREASE. SEE THE
 SIMPSON HIGH WIND RESISTANT CONSTRUCTION
 CATALOG.
  
 24) DETAIL 2 ON S4 SPECIFIES SIMPSON
 LTS 16 CONNECTORS FOR EACH TRUSS AND THE
 FRAMING PLAN ON S3 HAS (A) WHICH IS A
 LTS 12. PLEASE CORRECT.
  
 25) THE CONNECTOR SCHEDULE LISTS A
 SIMPSON MTT28B FOR (D) IS A TENSION TIE
 AND IS NOT APPROPRIATE FOR GIRDER TIE
 DOWN. SEE PAGE 9 OF THE SIMPSON HIGH
 WIND CATALOG. APPLICATION TYPICALLY
 REQUIRES BOLTING TO AN ADDITIONAL
 CONNECTOR ATTACHED TO A STUD BELOW THE
 TOP PLATE. SPECIFY BOTH CONNECTORS AND
 PROVIDE A DETAIL OF THE INSTALLATION.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW