2003-09-11 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 AMENDMENTS, CHAPTER
 ONE, ADMINISTRATION
 CODE.
  
 1) SHT A-3 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE REQUIREMENTS, NOR DOES IT
 REFLECT THE FLOOR PLAN.
 A) LAV AND KITCHEN SINK SHALL CONNECT
 TO THE STACK, NOT UNDERGROUND AS SHOWN.
 B) WATER CLOSED SHALL NOT BE TRAPPED ON
 THE RISER, THERE IS AN INTEGRAL TRAP IN
 THE FIXTURE. 1002.1
 C) A CLEANOUT IS REQUIRE 4' ABOVE THE
 FLOOR FOR THE WASH MACHINE. 708.10
 D) KITCHEN SINK IS LOCATED TO THE LEFT
 OF THE BATHROOM ON THE FLOOR PLAN AND TO
 THE RIGHT OF THE BATHROOM ON THE SANT.
 RISER DIAGRAM.
 2) SEE RED LINE CORRECTIONS FOR AN EX-
 AMPLE OF A RISER DIAGRAM THAT MEETS CODE
 REQUIREMENTS AND REFLECTS THE FLOOR PLAN
 3) 61G1-16.004(2) FIRM LICENSE NUMBER
 REQUIRED ON TITLE BLOCK FOR EACH SHEET.
  