| Notes |
| Date |
Text |
| 2003-09-11 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 AMENDMENTS, CHAPTER | | | ONE, ADMINISTRATION | | | CODE. | | | | | | 1) SHT A-3 SANITARY RISER DIAGRAM DOES | | | NOT MEET CODE REQUIREMENTS, NOR DOES IT | | | REFLECT THE FLOOR PLAN. | | | A) LAV AND KITCHEN SINK SHALL CONNECT | | | TO THE STACK, NOT UNDERGROUND AS SHOWN. | | | B) WATER CLOSED SHALL NOT BE TRAPPED ON | | | THE RISER, THERE IS AN INTEGRAL TRAP IN | | | THE FIXTURE. 1002.1 | | | C) A CLEANOUT IS REQUIRE 4' ABOVE THE | | | FLOOR FOR THE WASH MACHINE. 708.10 | | | D) KITCHEN SINK IS LOCATED TO THE LEFT | | | OF THE BATHROOM ON THE FLOOR PLAN AND TO | | | THE RIGHT OF THE BATHROOM ON THE SANT. | | | RISER DIAGRAM. | | | 2) SEE RED LINE CORRECTIONS FOR AN EX- | | | AMPLE OF A RISER DIAGRAM THAT MEETS CODE | | | REQUIREMENTS AND REFLECTS THE FLOOR PLAN | | | 3) 61G1-16.004(2) FIRM LICENSE NUMBER | | | REQUIRED ON TITLE BLOCK FOR EACH SHEET. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|