| 2003-10-03 00:00:00 | ****CORRECTIONS***** |
| | |
| | SAMANTHA THYNG, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | 1.)SEPARATE PERMITS REQUIRED. |
| | |
| | 2.)ADDITIONS OF OVER 25% MUST COMPLY |
| | WITH FBC3401.7.1.2, 2003 AMENDMENT. |
| | |
| | 3.)ENERGY CALCS REQUIRED; SIGN THE |
| | OWNER/AGENT LINE OF THE ENERGY CALC |
| | BEFORE SUBMITTING; FBC13-103.1.2. |
| | |
| | 4.)NOTE THAT IF THE SHORT FORM 600C |
| | PRESCRIPTIVE METHOD ENERGY CALC IS |
| | SUBMITTED, MINIMUM UNDER ATTIC |
| | INSULATION IS R30, MINIMUM BLOCK WALL |
| | INSULATION IS R5.REVISE TYPICAL WALL |
| | SECTION IF NECESSARY. |
| | |
| | 5.)TYPICAL WALL SECTION, THE BOTTOM |
| | OF THE FOOTER IS TO BE A MINIMUM OF 12" |
| | BELOW GRADE (NOTE STATES 8" MINIMUM), |
| | FBC1804.1.3. |
| | |
| | 6.)NOTE UNDER THE WIND INFORMATION |
| | REFERRING TO FBC2001 SHOULD INCLUDE |
| | 2003 REVISIONS AS WELL AS 2002. |
| | |
| | 7.)THE RETROFIT STRAP DETAIL (S3) |
| | SPECIFIES MTS20, A WOOD-TO-WOOD |
| | CONNECTOR IN A WOOD-TO-MASONRY |
| | APPLICATION.PLEASE ADDRESS. |
| | |
| | 8.)SUBMIT TWO COPIES OF PRODUCT |
| | APPROVALS FOR: |
| | VENTILATED DOOR |
| | DOOR W/SIDELITES |
| | IMPACT PROTECTION FOR VENTILATED DOOR |
| | IF REQUIRED (SEE PRODUCT APPROVAL) |
| | |
| | 9.)ADDITIONAL FEES DUE, $4.50 (RADON, |
| | SEE ATTACHED BZ231204). |