Plan Review Notes
Plan Review Notes For Permit 03090035
Permit Number 03090035
Review Stop B
Sequence Number 1
Notes
Date Text
2003-10-03 00:00:00****CORRECTIONS*****
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEPARATE PERMITS REQUIRED.
  
 2.)ADDITIONS OF OVER 25% MUST COMPLY
 WITH FBC3401.7.1.2, 2003 AMENDMENT.
  
 3.)ENERGY CALCS REQUIRED; SIGN THE
 OWNER/AGENT LINE OF THE ENERGY CALC
 BEFORE SUBMITTING; FBC13-103.1.2.
  
 4.)NOTE THAT IF THE SHORT FORM 600C
 PRESCRIPTIVE METHOD ENERGY CALC IS
 SUBMITTED, MINIMUM UNDER ATTIC
 INSULATION IS R30, MINIMUM BLOCK WALL
 INSULATION IS R5.REVISE TYPICAL WALL
 SECTION IF NECESSARY.
  
 5.)TYPICAL WALL SECTION, THE BOTTOM
 OF THE FOOTER IS TO BE A MINIMUM OF 12"
 BELOW GRADE (NOTE STATES 8" MINIMUM),
 FBC1804.1.3.
  
 6.)NOTE UNDER THE WIND INFORMATION
 REFERRING TO FBC2001 SHOULD INCLUDE
 2003 REVISIONS AS WELL AS 2002.
  
 7.)THE RETROFIT STRAP DETAIL (S3)
 SPECIFIES MTS20, A WOOD-TO-WOOD
 CONNECTOR IN A WOOD-TO-MASONRY
 APPLICATION.PLEASE ADDRESS.
  
 8.)SUBMIT TWO COPIES OF PRODUCT
 APPROVALS FOR:
 VENTILATED DOOR
 DOOR W/SIDELITES
 IMPACT PROTECTION FOR VENTILATED DOOR
 IF REQUIRED (SEE PRODUCT APPROVAL)
  
 9.)ADDITIONAL FEES DUE, $4.50 (RADON,
 SEE ATTACHED BZ231204).