| 2003-10-06 00:00:00 | OK FOR HISTORIC (PLANS NOT STAMPED) |
| | PER SP |
| 2003-10-02 00:00:00 | ******CORRECTIONS***** |
| | |
| | SAMANTHA THYNG, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | 1.)ADDITIONAL PERMITS REQUIRED. |
| | |
| | 2.)ENGINEER'S LICENSE NUMBER IS |
| | REQUIRED ON THE TITLE BLOCK, FAC |
| | 61G15-23.002. |
| | |
| | 3.)SHOW THE WINDOW SIZES, TYPE AND |
| | SILL HEIGHT FOR BEDROOMS.COMPLY WITH |
| | FBC1005.4. |
| | |
| | 4.)IT IS NOT CLEAR AS TO HOW SIMPSON |
| | H10 IS TO BE INSTALLED (EXTERIOR WALL |
| | SECTION).CLARIFY. |
| | |
| | 5.)PROVIDE DIMENSIONS FOR THE EXTERIOR |
| | WALL.FIRESTOP MAY BE REQUIRED FBC |
| | 705.3. |
| | |
| | 6.)CHANGES DRAWN ON THE PLAN MUST |
| | BE INITIALED AND DATED BY THE ENGINEER. |
| | |
| | 7.)PROVIDE SPACING FOR THE 1/2"X6" EXP |
| | BOLTS (EXTERIOR WALL SECTION). |
| | |
| | 8.)IMPACT PROTECTION REQUIRED FBC1606. |
| | 1.4.PROVIDE A HURRICANE SHUTTER |
| | ATTACHMENT DETAIL. |
| | |
| | 9.)THE ATTACHMENT SPECIFIED IN THE |
| | WOOD HEADER DETAIL, TP#X, IS NOT IN THE |
| | USP2003 CATALOG.CLARIFY. |
| | |
| | 10.) NAILING FOR THE USP RS100 CONFLICTS |
| | WITH THE CATALOG.CLARIFY. |
| | |
| | 11.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 12.)PROVIDE A STRUCTURAL DETAIL FOR |
| | THE STAIRS AS IT APPEARS THAT THEY ARE |
| | TO BE REPAIRED OR REPLACED. FIREBLOCKING |
| | REQUIRED AT STAIRS FBC2305.1.4. |
| | |
| | 13.)IMPROVEMENTS OVER 50% OF VALUE |
| | ARE TO COMPLY WITH FBC3401.7.2.6. |
| | |
| | 14.)PROVIDE A HANDRAIL DETAIL. |
| | |
| | 15.)PROVIDE A SURVEY FOR THIS JOB. |
| | |
| | 16.)THE WINDOW PRODUCT APPROVAL IS NOT |
| | COMPLETE. |
| | |
| | 17.)PROVIDE TWO COPIES OF PRODUCT |
| | APPROVALS FOR: |
| | SINGLE HUNG WINDOW |
| | FRONT DOOR |
| | IMPACT PROTECTION |
| | PRODUCT APPROVALS MAY BE AVAILABLE AT |
| | WWW.MIAMIDADE.GOV (FIND A DEPT, BUILDING |
| | CODE COMPLIANCE, PRODUCT CONTROL, SEARCH |
| | APPROVED PRODUCTS). |