Plan Review Notes
Plan Review Notes For Permit 03081864
Permit Number 03081864
Review Stop P
Sequence Number 2
Notes
Date Text
2003-10-25 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SANITARY RISER DIAGRAM DO NOT MEET
 CODE REQUIREMENTS NOR DO THEY REFLECT
 THE FLOOR PLAN.
 POWDER ROOM: LAV NOT VENTED. "S" TRAPS
 NOT APPROVED SECTION 1002.3(5)
 KITCHEN: ISLAND SINK TO CONNECT ON THE
 HORIZONTAL BLDG DRAIN. DISHWASHER SHALL
 CONNECT TO THE TAILPIECE OF THE SINK.
 BAR SINK: SHALL CONNECT ON THE HORIZONT-
 AL BLDG. DRAIN AND HAVE A SEPARATE STACK
 MASTER BATHS: TUB WITH WATER CLOSETS IS
 NOT VENTED. FIXTURES NOT VENTED ON OTHER
 STACK, LAVS ARE "S" TRAPPED AND BOTH
 LAVS ARE NOT ON THE SAME SIDE OF THE
 WALL.
 2) SUBMIT A RISER DIAGRAM SHOWING ALL
 THE HORIZONTAL BUILDING DRAIN AND SHOW-
 ING WHERE THE STACKS TIE IN.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]