Plan Review Notes
Plan Review Notes For Permit 03081864
Permit Number 03081864
Review Stop E
Sequence Number 2
Notes
Date Text
2003-10-24 00:00:00************** UNSAT ****************
  
 1)NOTE: PLEASE SEE THAT PLANS ARE NOW
 COMING BACK ADDING A NEW SERVICE.
 THE NEW SERVICE IS NOT PERMITTED. 230.2
 PLEASE ALSO NOTE, OLD SERVICE WILL BE
 REQ'D TO BE CHANGED IN ORDER TO TAKE OUT
 SECOND METER CAN. ONLY TWO(2) METERS
 TOTAL ARE PERMITTED PER ZONING.
 REMOVAL OF METER ALONE WILL NOT MEET
 REQUIREMENT. PLEASE ADJUST SERVICE.
 A MCB AT MAIN HOUSE IS STILL REQ'D.
 225.31
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]