| Plan Review Notes For Permit 03081864 |
| Permit Number |
03081864 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-09-19 00:00:00 | ************** UNSAT ******************* | | | | | | 1)NOTE: PLEASE SEE RISER, SHOWS MAIN | | | DISC FOR PANEL "A" AT DETACHED BLDG/ | | | COTTAGE. PLEASE SEE 225.31 FOR MEANS | | | OF DISC REQ'D. | | | PLANS DO NOT INDICATE MCB. | | | | | | 2)NOTE: PLEASE SEE PLANS, SHOWS LOCATION | | | FOR PANEL 'A' BUT PANEL 'B' IS NOTED | | | TO BE IN AREA BUT NOT SHOWN? | | | PLEASE SHOW. | | | | | | 3)NOTE: PLEASE CLARIFY/ SHOW COLD WATER | | | BOND FOR SERVICE GROUNDING SYSTEM. | | | 250.50,250.32 | | | | | | 4)NOTE: PLEASE LIST THE REQ'D ARC FAULT | | | PROTECTED CIRCUITS PER 210.12 | | | | | | 5)NOTE: PLEASE SEE MISSING RECEPTS IN | | | MAST BEDRM. 210.52 | | | | | | 6)NOTE: PLEASE SEE PANEL "A", PANEL | | | DETAIL INDICATES CIRCUITS 27,29 TO BE | | | GFI AND YET 27/29 FEED PANEL "B"? | | | PLEASE CLARIFY. | | | | | | 7)NOTE: PLEASE SUBMIT AIC RATING(S) FOR | | | NEW MAIN. 110.9/215.5 | | | | | | 8)NOTE: PLEASE SEE FAC 61G15-23.002, | | | PLEASE PROVIDE CETIFICATE OF AUTHORIZAT- | | | -ION # ON TITLE BLOCK. FS 471 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|