2003-09-19 00:00:00************** UNSAT *******************
  
 1)NOTE: PLEASE SEE RISER, SHOWS MAIN
 DISC FOR PANEL "A" AT DETACHED BLDG/
 COTTAGE. PLEASE SEE 225.31 FOR MEANS
 OF DISC REQ'D.
 PLANS DO NOT INDICATE MCB.
  
 2)NOTE: PLEASE SEE PLANS, SHOWS LOCATION
 FOR PANEL 'A' BUT PANEL 'B' IS NOTED
 TO BE IN AREA BUT NOT SHOWN?
 PLEASE SHOW.
  
 3)NOTE: PLEASE CLARIFY/ SHOW COLD WATER
 BOND FOR SERVICE GROUNDING SYSTEM.
 250.50,250.32
  
 4)NOTE: PLEASE LIST THE REQ'D ARC FAULT
 PROTECTED CIRCUITS PER 210.12
  
 5)NOTE: PLEASE SEE MISSING RECEPTS IN
 MAST BEDRM. 210.52
  
 6)NOTE: PLEASE SEE PANEL "A", PANEL
 DETAIL INDICATES CIRCUITS 27,29 TO BE
 GFI AND YET 27/29 FEED PANEL "B"?
 PLEASE CLARIFY.
  
 7)NOTE: PLEASE SUBMIT AIC RATING(S) FOR
 NEW MAIN. 110.9/215.5
  
 8)NOTE: PLEASE SEE FAC 61G15-23.002,
 PLEASE PROVIDE CETIFICATE OF AUTHORIZAT-
 -ION # ON TITLE BLOCK. FS 471
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  