| Plan Review Notes For Permit 03081857 |
| Permit Number |
03081857 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-09-24 00:00:00 | *****CORRECTIONS****** | | | | | | SAMANTHA THYNG, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)THERE IS AN EXISTING WINDOW ON THE | | | EXTERIOR WALL AT THE PROPOSED BATHROOM | | | TO COMPLY WITH THE MECHANICAL PROVISO | | | (AS PER CONVERSATION WITH CONTRACTOR). | | | SHOW ON THE PLAN. | | | | | | 2.)PROVIDE AREA CALCULATION ON THE | | | PLAN - EXISTING, PROPOSED, NEW TOTALS | | | FOR A/C AND UNCONDITIONED SPACE. | | | | | | 3.)IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY.THE PLANS MUST BE STAMPED | | | AND THE RECEIPT ATTACHED TO THE | | | APPLICATION.233-5025 | | | | | | 4.)THE PLAN SHOWS "EXISTING ENCLOSED | | | PORCH".PROVIDE A WALL DETAIL WITH | | | STRUCTURAL INFORMATION, INCLUDING | | | ATTACHMENTS CONTINUOUS FROM FOUNDATION | | | THROUGH THE ROOF FBC104.3.1.1. (EXTERIOR | | | WALL), TO COMPLY WITH FBC. | | | | | | 5.)ENERGY CALCS REQUIRED, FBC13-103.1. | | | 2. | | | | | | 6.)PROVIDE A WALL SECTION FOR THE | | | INTERIOR PARTITION WALL, INCLUDING | | | FIRESTOP AND INSULATION. | | | | | | 7.)SHOW EMERGENCY EGRESS FOR THE | | | BEDROOM, FBC1005.4. |
|