| 2003-10-15 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER-11 |
| | |
| | 1) FROM PREVIOUS REVIEW: SHT A.5.3, DE- |
| | TAIL #6, BREAKROOM SINK SHALL COMPLY |
| | WITH SECTION 11-4.24 AND ALL SUBSECTIONS |
| | PROVIDE DETAILS, SHOW CLEAR FLOOR SPACE, |
| | HEIGHT & CLEARANCES, FAUCETS, PIPES AND |
| | SURFACES, ECT. |
| | 2) FROM PREVIOUS REVIEW: FOR GAS REVIEW, |
| | D. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2001 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.5.2 AND TABLES 402(1) THRU |
| | 402(34). |
| | E. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2 |
| | 3) SHT P3 PLUMBING SPECS #7, AIR CHAMB- |
| | ERS NOT APPROVED. DELETE REFERENCE. |
| | 4) SHT P5 WATER RISER DIAGRAM, AIR CHAM- |
| | BERS NOT APPROVED. SEC 604.9 IF WATER |
| | HAMMER ARRESTORS THEY SHALL BE LOCATED |
| | NEAR THE FIXTURE, NOT IN THE CEILING. |
| | PDI-WH 201 AND MANUF. INSTALLATION IN- |
| | STRUCTIONS. |
| | |
| | REVIEW BY KEN STEVENS |