| 2003-09-12 00:00:00 | THIS BUILDING IS LOCATED IN THE |
| | DESIGNATED FIRE DISTRICT.TYPE VI |
| | CONSTRUCTION,(IE WOOD FRAME) IS NOT |
| | PERMITTED.SOME OF THE EXTERIOR |
| | ARCHITECTURAL FEATURES PROPOSED SHOW |
| | WOOD STUDS AND WALL SHEATHING.PLEASE |
| | REVISE AS NECESSARY.SEE FBC F102.1 AS |
| | AMENDED BY THE CITY OF WEST PALM BEACH. |
| | |
| | ARCHITECTURAL TRIM IS REQUIRED TO BE |
| | NON-COMBUSTIBLE OR FRT WOOD. SEE FBC |
| | F102.2.7.IS THE FYPON MATERIAL |
| | NON-COMBUSTIBLE AS DEFINED IN FBC 202. |
| | |
| | PLEASE PROVIDE SPECIFIC CONSTRUCTION |
| | DETAILS FOR THE SUSPENDED DRYWALL AND |
| | PANELCEILINGS.INCLUDE FASTENERS, |
| | MATERIALS AND CONNECTION METHODS. FBC |
| | 104.2. |
| | |
| | THE VARIOUS SECURITY GATES SHOWN MUST |
| | COMPLY WITH FBC 1020.3 AND 1012.1.7. |
| | |
| | THE REQUIRED EXTERIOR EGRESS DOORS MUST |
| | COMPLY WITH FBC 1012.5 SWING OVER PUBLIC |
| | ROW, 1003.2.3 CLEAR WIDTH, |
| | PARTICULARLY SINGLE LEAF OF DOUBLE |
| | DOOR,SEE ALSO FBC 11-4.13. |
| | |
| | THE NOTES AND SPECIFICATIONS PAGES ARE |
| | RECOGNIZED TO THE EXTENT THAT THEY ARE |
| | NOT IN CONFLICT WITH THE FBC 2001 WITH |
| | 6/03 REVISIONS AND STANDARDS AND |
| | REFERENCES OF THE FBC. |