| 2003-10-10 00:00:00 | PROVISO: | | | FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | | REQUIRED AS PER 2001 FBC(M) 606.2.1 AND | | | SHALL HAVE NOTIFICATION TO ALARM/STROBE | | | IN NORMALLY OCCUPIED AREAS AS PER NFPA | | | 90A 4-4.4.3.PLEASE NOTE, DUCT SMOKE | | | DETECTORS SHALL BE INSTALLED IN THE | | | SUPPLY DUCT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|