Notes
Date Text
2003-10-10 00:00:00PROVISO:
 FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 REQUIRED AS PER 2001 FBC(M) 606.2.1 AND
 SHALL HAVE NOTIFICATION TO ALARM/STROBE
 IN NORMALLY OCCUPIED AREAS AS PER NFPA
 90A 4-4.4.3.PLEASE NOTE, DUCT SMOKE
 DETECTORS SHALL BE INSTALLED IN THE
 SUPPLY DUCT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.