2003-10-08 00:00:00*********** UNSAT ****************
  
 1)NOTE: PLEASE SEE THAT TITLE BLOCK FOR
 ENGINEERS AHS BEEN REMOVED AND ARCH IS
 NOW PRESENT.
 PLEASE SEE FS 471.003H2AAND SEE
 FBC 104.4.1.3. ELECTRICAL SYSTEMS OF
 277/480V MUST BE DESIGNED, SIGNED,DATED
 AND SEALED BY AN ENGINEER. ORIG PLANS
 HAD ENGINEER TITLE BLOCK WHICH LETTER
 EXPLAINS IT WAS SUBMITTED IN ERROR.
 PLANS WILL STILL BE REQ'D TO HAVE A
 TITLE BLOCK FOR ENGINEER WHICH MAY OR
 MAY NOT INCLUDE A CA #.
 61G15-23.002/ 471.025
  
 PLEASE SEE THAT ELECTRICAL COMMENTS
 SEEM TO BE ADDRESSED. PLANS WILL BE
 GOING BACK TO BLDG AND MECH PLAN REVIEW
 DUE TO REVISED B&M SHEETS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  