| Notes |
| Date |
Text |
| 2003-09-24 00:00:00 | PROVISO: | | | 1.PLEASE NOTE OUTSIDE AIR INTAKE | | | SHALL BE LOCATED A MINIMUM OF 10 FT FROM | | | LOT LINES OR BUILDINGS ON THE SAME LOT. | | | WHERE OPENINGS FROM ON A STREET OR | | | PUBLIC WAY, THE DISTANCE SHALL BE | | | MEASURED TO THE CENTERLINE OF STREET OR | | | WALKWAY. | | | | | | 2.FAN SHUTDOWN REQUIRED WITH NOTIFICAT | | | NOTIFICATION TO ALARM/STROBE AS PER | | | 2001 FBC(M) 606.2.1 & NFPA 90A 4-4.4.3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|