2003-09-24 00:00:00PROVISO:
 1.PLEASE NOTE OUTSIDE AIR INTAKE
 SHALL BE LOCATED A MINIMUM OF 10 FT FROM
 LOT LINES OR BUILDINGS ON THE SAME LOT.
 WHERE OPENINGS FROM ON A STREET OR
 PUBLIC WAY, THE DISTANCE SHALL BE
 MEASURED TO THE CENTERLINE OF STREET OR
 WALKWAY.
  
 2.FAN SHUTDOWN REQUIRED WITH NOTIFICAT
 NOTIFICATION TO ALARM/STROBE AS PER
 2001 FBC(M) 606.2.1 & NFPA 90A 4-4.4.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.