Plan Review Notes
Plan Review Notes For Permit 03081707
Permit Number 03081707
Review Stop E
Sequence Number 1
Notes
Date Text
2003-09-08 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE SEE COPY OF FAC 61G1-16.
 004.PLEASE SEE THAT FIRM'S AA# IS REQ'D
 ON TITLE BLOCK ALSO. PER FS 481
 **ALL SHEETS, NOT ONLY ELECTRICAL.
 2)NOTE: PLEASE SEE THAT ALL CONTINUOUS
 LOADS ARE TO BE SHOWN AT 125%. 215.3/
 230.42 ETC.
  
 3)NOTE: PLEASE SHOW CALCULATIONS FOR
 TRACK LIGHTING PER 220.12B
  
 4)NOTE: PLEASE SEE CODES REFERENCED ON
 PLANS, THEY ARE FROM THE 1996 NEC,
 PLEASE SEE THAT WE ARE NOW UNDER 2002
 NEC AND ALL CODES REF. SHOULD CORRELATE.
  
 5)NOTE: PLEASE SUBMIT AIC RATING FOR
 NEW MAIN ALSO. 110.9/215.5
  
 6)NOTE: PLEASE SHOW GROUNDING ATTACH-
 -MENT FOR TRANSFORMER PER 250.30
  
 7)NOTE; PLEASE SEE NEC FOR TRANSFORMER
 CONNECTIONS, PLAN SHOW EMT TO AND FROM
 X-FORMER, PLEASE NOTE, THESE ARE TO BE
 FLEXIBLE CONNECTIONS W/ EQUIPMENT
 GROUNDING CONDUCTORS. 250.110, 450.10,
 300.10 ETC DUE TO VIBRATION OF TRANS-
 FORMER.
  
 8)NOTE: PLEASE ALSO SHOW LARGEST MOTOR
 LOAD AT 125%.
  
  
 PLEASE REMOVE ALL OLD VOIDED SHEEST AND
 INSERT NEW SHEETS INTO TWO COMPLETE SETS
 FOR REVIEW AND STAMPING. ONE SET OF OLD
 SHEETS MAY NEED TO BE RESUBMITTED FOR
 REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  