| Plan Review Notes For Permit 03081577 |
| Permit Number |
03081577 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-09-16 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION AND RESUBMIT FOR REVIEW. | | | | | | 1} PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 2} PLEASE PROVIDE LOAD CALCULATIONS FOR | | | FOR ALL UNITS PER 215-5. | | | | | | 3} PLEASE INDICATE THE SIZE AND TYPE OF | | | ALL RACEWAYS AND CONDUCTORS BEING | | | INSTALLED. | | | | | | 4} PLEASE INDICATE THE GEC SYSTEM SIZE | | | AND COMPLIANCE WITH ARTICLE 250.50. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|