Plan Review Notes
Plan Review Notes For Permit 03081548
Permit Number 03081548
Review Stop E
Sequence Number 1
Notes
Date Text
2003-09-08 00:00:00*************** UNSAT ***************
  
 1)NOTE: PLEASE SEE PLANS, ALL CODES AND
 NOTES REFERENCE TO THE 99 NEC.
 PLEASE NOTE WE ARE NOW UNDER THE 2002
 NEC AND ADJUST ARTS ACCORD.
  
 2)NOTE: PLEASE CORRELATE RISER AND PANEL
 SCHEDULES FOR A/C COND OCP. RISER SHOWS
 40A OCP AND PANELS SHOW 30A?
  
 3)NOTE: PLANS MENTION ALL AS-BUILTS AND
 REVISIONS ARE TO DONE BEFORE FINAL,
 PLEASE NOTE, THESE ARE NOW REQ'D BEFORE
 ROUGH****.
  
 4)NOTE: PLEASE SUBMIT/SHOW AIC RATINGS
 FOR MAINS AND PANELS. 110.9/215.5
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  